Fixing of Conduit:<br />

Conduit pipes shall be fixed by heavy gauge clamps, secured to suitable wood plugs<br />

or other approved plugs with screws in an approved manner at an interval of not<br />

more than one metre but on either side of the couplers, bends, or similar fittings,<br />

saddles shall be fixed at a distance of 30 cm from the centre of such fittings. The<br />

saddle should not be less than 24 gauge for conduits upto 25mm dia. and not less<br />

than 20 gauge for larger diameter.<br />

Where conduit pipes are to be laid along the trusses, steel joints etc. the same shall<br />

be secured by means of ordinary clips or girder lips as required by the Engineer-incharge.<br />

Where it is not possible to drill holes in the truss members, suitable clamps<br />

with bolts and nuts shall be used. The width and the thickness of the ordinary clips<br />

or girders clips and clamps shall not be less than as stated below:<br />

Switch Box:<br />

Switch box shall be made of metal on all sides, except on the front.<br />

In the case of cast boxes, wall thickness shall be at least 3 mm and in case of<br />

welded mild steel sheet boxes the wall thickness shall not be less than 18 gauge for<br />

boxes, upto a size of 20cm x 30cm and above this M.S. boxes shall be used. Except<br />

where otherwise stated 3 mm thick phenolic laminated sheets like sunmica shall be<br />

fixed on the front with brass screws. Clear depth of the box shall not be less than<br />

60 mm and this shall be increased suitably to accommodate mounting of fan<br />

regulators inflush pattern. All fittings shall be flush pattern. Only a portion of the<br />

above box shall be sunk in the wall, the other portion being projected out for<br />

suitable entry of conduit pipes into the box.<br />

Conduit Wiring System<br />

Conduit wiring system shall comply with all the requirements of surface conduit<br />

wiring system specified in clauses above and in addition to the requirements<br />

specified in the following clauses.<br />

The chase in the wall shall be neatly made and ample dimensions to permit the<br />

conduit to be fixed in the manner desired. In the case of buildings under<br />

construction, fixed work, special care shall be taken to fix the conduit and<br />

accessories in position along within the building work, to avoid damage to the<br />

finished wall etc.<br />

GTS : General Technical Specification. Page 128