5 Amps and 15 Amps socket outlet shall normally be fixed at any convenient space<br />

23 cms above the floor level or near such levels in special cases as desired by the<br />

Engineer-in-charge. 15 Amps switch and socket should be an integral provisions of<br />

an indicator diode. The switch for 5 Amps socket outlet shall be kept along with<br />

socket outlet. However, in special case, if desired by the Engineer the 5 Amps.<br />

socket outlet shall be kept at normal switch level and that for 15 Amp along with<br />

the socket outlet. However, in special case, if desired by the Engineer the 5 Amp<br />

socket outlet shall be placed at the normal switch level.<br />

Where socket outlet are placed at lower levels, they shall be enclosed in a suitable<br />

metallic box, as the case may be to harmonise with the system or wiring adopted. In<br />

an earthed system of supply a socket outlet and plug shall be of the three pin type.<br />

The third terminal shall be connected to earth.<br />

Conductors connecting electrical appliance with a socket outlet shall be of flexible<br />

twin cord with an earthing cored which shall be secured by connecting between the<br />

earth terminal of plug and the metallic body of the electrical appliance.<br />

Attachment of Fittings and Accessories :<br />

In case of conduit wiring, all accessories like switches sockets, outlets, call bell<br />

pushes and regulators shall be fixed in flush pattern inside metal boxes.<br />

Accessories like ceiling roses, brackets, battens, stiff pendants, etc. shall be fixed on<br />

metal outlet boxes.<br />

Aluminium alloy or cadmium platted iron screws shall be used to fix the accessories<br />

to their bases. The blocks/board shall normally be mounted with their bottom<br />

1.25 m from floor level. The Boards shall have a sunmica finish.<br />

Surface Conduit Wiring System :<br />

Conduit pipes of approved gauge thickness shall be used. The maximum number of<br />

VIR/PVC insulated 250 volts grade aluminum conductor cable that can be drawn in<br />

one conduit of various sizes and the number of cables per conduit shall not be<br />

exceeded. The minimum conduit disconnector shall not be less than 25 mm.<br />

In long distance straight run of conduit, inspection type junction box at reasonable<br />

intervals shall be provided.<br />

GTS : General Technical Specification. Page 127