A conductor shall be carried in an approved heavy gauge solid drawn or lap welded<br />

conduit or in a porcelain tube of such a size that it permits easy drawings in. The<br />

ends of conduit shall be neatly bushed with porcelain, wood or other approved<br />

material.<br />

Where a wall tube passes outside a building so as to be exposed to weather, the<br />

outer end shall be well mounted and turned downwards and properly bushed on the<br />

open end.<br />

Fixing to walls and ceiling:<br />

Plug for ordinary walls or ceiling shall be of well seasoned teak or other approved<br />

hard wood not less than 5 cm. long by 25 cm. sq. on the inner and 2 cm. sq. on the<br />

outer end. They shall be cemented into walls within 6.5 mm of the surface the<br />

remainder being finished according to the nature of the surface with plaster.<br />

Where owing to irregular coarsing or other reasons the plugging of the walls or<br />

ceiling with wood plugs present difficulties, the wood casing, wood batten or metal<br />

conduit shall be attached to the wall or ceiling in an approved manner. In the case<br />

of white washing. Plugging of walls or ceiling can be done in a better way where<br />

neatness is the first consideration. In all such case approver type of asbestos or<br />

fiber fixing plug (Rawl or Phil plug) with correct size of tees shall be used and done<br />

in a workman like manner. Were this cannot be done, wooden plugs as described<br />

can be used with special permission of the Engineer.<br />

Fittings:<br />

Lights, fans and sockets outlets shall be so located as to provide maximum comfort<br />

to the occupant and to enable him to utilise the electricity in the most economical<br />

manner.<br />

Where conductors are required to be drawn through tube or channel leading to the<br />

fitting, the tube or channel must be free from sharp angles or projecting edges.<br />

Non-flammable shade form a part of a light fitting against all risks or fire, celluloid<br />

shade or light fitting shall not be used under any circumstances. Vitreous enameled<br />

iron shade shall be of size 250mm x 90mm (nominal) size with a tolerance to<br />

5mm). Plastic shade shall not be generally used in the fittings suitable for<br />

incandescent lamp.<br />