Drawings:<br />

All wiring diagrams shall indicate clearly in plan, the main switch board, the<br />

distribution fuse board, the run of various mains and sub-mains and the position of<br />

all points with their classification<br />

Cables:<br />

All cables shall conform to the relevant Indian Standard. Conductors of all cables<br />

except the flexible cable shall be of aluminum.<br />

The smallest aluminum conductors for the final circuit shall have a nominal crosssectional<br />

area of not less than 2.5 sq.mm. The minimum size of aluminium<br />

conductors for power wiring shall be 4 sq.mm. (1/2.24 mm).<br />

Rating of Lamp, Fans, Socket outlet points and Exhaust fans:<br />

Incandescent lamps installed in pump house & other means shall be rated at<br />

60 watts and 100 watts respectively.<br />

Table fans and ceiling fans shall be rated at 60 watts. Exhaust fans shall be rated<br />

according to their capacity.<br />

5 Amps. socket outlet points and 15 amp. socket outlet points shall be rated at<br />

100 watts and 1000 watts respectively, unless the actual values of load are known or<br />

specified.<br />

Joint and Looping Back<br />

Unless otherwise specified, the wiring shall be done in the “Looping System”.<br />

Phase of live conductors shall be looped at the switch box and neutral conductor can<br />

be looped from the light, fan or socket outlet. In non-residential buildings, neutral<br />

conductor and earth conductor and earth continuity wire shall be brought to each<br />

switch board situated in room and halls. These shall be terminated inside the switch<br />

boards with suitable connectors and the switch board shall be of adequate size to<br />

accommodate one number 5 amp. socket outlet and control switch in future.<br />

GTS : General Technical Specification. Page 122