Point Wiring:<br />

Point wiring shall include all work necessary to complete wiring from switch circuit<br />

of any length from the tapping point on the distribution circuit switch board to the<br />

following.<br />

- Ceiling rose for fans, Lighting etc.<br />

- Socket outlet (in the case of socket outlet points).<br />

- Lamp holder (in the case of wall brackets, batten points, bulk head and<br />

similar fittings).<br />

- Call bell buzzer (in the case of the works “via the ceiling rose/socket outlet<br />

or bell push where no ceiling rose/socket outlet is provided”).<br />

Circuit Wiring:<br />

Circuit wiring shall mean the length of wiring from the distribution board upto the<br />

tapping point of the nearest first points of that circuit, viz., upto the nearest first<br />

switch board measured along the run of wiring. Such wiring shall be measured on<br />

linear basis.<br />

System of Wiring:<br />

The wiring shall be carried out on such a system as may be specified in the tender<br />

schedule or otherwise specified in the special specification (“Power” and “Heating”<br />

wiring shall be kept separate and distinct from “Lighting” and “Fan” wiring).<br />

Recessed conduit wiring shall be done on distribution system main and branch<br />

distribution boards at convenient physical and electrical centers and without fuses at<br />

isolated places. All conductors shall run, as far as possible, along the walls and<br />

ceiling so as to be easily accessible and capable of being thoroughly inspected. In<br />

no case, the open wiring shall be run above the false ceiling without the approval of<br />

Engineer-in-Charge. In all type of wiring due consideration shall be given for<br />

neatness, good appearance and safety.<br />

Balancing of circuits:<br />

The balancing of circuits in three phase installations shall be arranged before hand<br />

to the satisfaction of Engineer.<br />