Testing of Cables:<br />

Once the cable is laid, following tests shall be conducted in presence of the<br />

departmental representatives authorized by Engineer, before energizing the cable.<br />

1. Insulation resistance test (Sectional and Overall).<br />

2. Sheathing continuity test.<br />

3. Continuity and conductor resistance test.<br />

4. Earth test.<br />

5. High voltage test.<br />

Teat conducted shall be as per Indian standard and National Electrical code.<br />

15.14 Control Switches.<br />

Control and instrument switches shall be of rotary type flush mounting having<br />

enclosed contacts which are accessible by the removal of cover and shall be<br />

provided with properly designated escutcheon plates clearly marked to show the<br />

operating positions. Control switches shall have momentary contacts, spring return<br />

to centre with pistol grip handle. Instrument and selector switches shall have oval<br />

knob.<br />

15.15 Push Buttons.<br />

Push buttons shall be of momentary contact type with rear terminal connections.<br />

The colour of the push buttons shall be “Green” for start and “Red” for stop.<br />

Whether required, the push button shall be suitably shrouded to prevent inadvertent<br />

operations. They shall be provided with integral inscription plates engraved with<br />

their functions. The contact element shall have at least 1 No. and 1 NC contacts.<br />

The contacts shall be able to make and carry at least 6 Amp at 415 AC.<br />

15.16 Indicating Lamps.<br />

Indicating lamps shall be panel mounting type with rear connection. The lamps<br />

shall be provided with the built-in series resistors on the lamp holder. The lamp<br />

shall have translucent lamp cover, of suitable colour. The cover shall be oil and<br />

dust proof poly-carbonate lense. The bulb and lenses shall be interchangeable and<br />

replaceable from front of the panel.<br />

GTS : General Technical Specification. Page 119