2. The cables shall conform to the latest editions of following IS and other<br />

relevant IS mentioned therein<br />

IS 7098 (Part-<strong>II</strong>): Specifications for cross linked polyethylene Insulated<br />

PVC sheathed cables for working voltages from 3.3 KV<br />

up to and including 33 KV.<br />

Drawings and Schedules:<br />

Sizes of cables shall be given in single line power diagrams. A cable schedule shall<br />

be prepared on the basis of relevant drawings. All cable and wires shall be<br />

adequately sized to carry continuously the normal currents expected on the relative<br />

circuits. All trenches for electrical cables shall be separate from water or sewage<br />

pipe line trenches.<br />

Splicing and Termination:<br />

Straight through joints shall be avoided. In case, these are absolutely necessary<br />

they shall be made at convenient locations suitably protected as approved and<br />

sanctioned by the Engineer-in-charge but in no case within the conduit pipes or<br />

ducts. Branch circuit wiring shall be spliced only in switch boxes, panel switch<br />

socket outlet boxes light fixtures outlets and circular junction boxes. They shall be<br />

made only with approved porcelain connectors.<br />

Cable glands for strip armored cables shall include a suitable armour clamps for<br />

receiving and securely attaching the armoring of the cable in a manner such that no<br />

movement of the armour occurs when the assembly is subjected to tension forces.<br />

The cable gland shall not imposed on armoring, a bending radius not less than<br />

15 times the diameter of the cable. The clamping ring shall be solid and adequate<br />

strength.<br />

Provision shall be made for attachment of an external earthing bond between the<br />

clamp of the cable and the metallic structure of the apparatus to which the cable box<br />

is attached.<br />

Compression type cable end glands shall be used for cable connections. Double<br />

compression cable end glands shall be used for flame proof switch gears. Cable<br />

glands shall be of brass with cadmium or nickel plating.<br />

Tinned copper lugs shall be used for cable termination.<br />

Cables shall be tested in accordance with IS:1554 / 7098<br />