While removing the cable from the drum, it shall be ensured that the cable drum is<br />

supported on suitable jacks and the drum is rotated to unwind the cable from the<br />

drum. The cable should never be pulled while unwinding from drum. It shall be<br />

ensured that the cables are run over suitable wooden rollers placed in the trench at<br />

intervals not exceeding 2 meters.<br />

In routing, necessary barriers and spacing shall be maintained for cables of different<br />

voltages in case they lie side by side. Telephone cables shall cross the power cables<br />

only at about right angles and these two shall not run in close proximity. LT cables<br />

shall be bent in radius not less than 12 times their individual overall diameters.<br />

Routes of these cables shall be arrived at on the basis of the relevant drawings and<br />

after consulting the Engineer.<br />

Contractor shall provide all necessary labour, tools, plants and other requisites at his<br />

own cost; for carrying out pumping of water and removing of water from trenches if<br />

required anywhere at the time of execution.<br />

H.T. Cables:<br />

H.T. 11 KV grade suitable rating 3 core XLPE aluminum conductor cable minimum<br />

size 150 mm 2 from PHED supply point to 6.6Kv MCC of pump houses.<br />

Specifications for H.T. Cables:<br />

This specification covers the requirements of high voltage cables and associated<br />

accessories like straight joints and termination's etc. The cable sizes shall be<br />

calculated based on the fault level of the local system. Minimum size of HT cables<br />

shall be 150 mm 2 in case of XLPE cables.<br />

Codes and standards:<br />

1. The design manufacture and performance of the cables shall comply with all<br />

currently applicable statutes regulations, and safety codes in the locality where<br />

they will be installed. Nothing in this specification shall be construed to relieve<br />

the Contractor of his responsibility in this regard.<br />

GTS : General Technical Specification. Page 117