16.08.2013 Views

PACKAGE : I Bid Document VOLUME : II - Public Health Engineering

PACKAGE : I Bid Document VOLUME : II - Public Health Engineering

PACKAGE : I Bid Document VOLUME : II - Public Health Engineering

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Contactors:<br />

The three pole contactors with minimum of 2 No. + 2 NC working contacts and one<br />

number of 1 No + 1 NC spare contact shall be used. The contact made of anti-weld<br />

silver cadmium shall be designed to give minimum bounce to ensure long contact<br />

life. The rating of the contactor shall suit the motor and capacitor circuit duty. The<br />

contactor shall be suitable for 415V, 50Hz, AC 3 phase duty in respect of making<br />

and breaking operations at specified power factors. The contactors shall conform to<br />

IS:13947 Part-1 and Part-4.<br />

Single Phase Preventor:<br />

The single phasing preventor shall be provided for all 415 V, motors above 5 kW<br />

rating. The single phasing preventor shall be current operated type using minimum<br />

current detection/negative phase principle. Necessary current transformers shall be<br />

provided to suit the requirement of the single phasing preventor. The single phasing<br />

preventor shall be stable during the starting of the motor. The maximum operating<br />

time to the single phasing preventor shall not exceed 2/3 second even in the starting<br />

condition of motor.<br />

15.13 Cables and cable laying.<br />

Following type of cables shall be used.<br />

1. For LT Power Supply : 3½ core, 3 core or 2 core 1100/600 V PVC<br />

insulated PVC sheathed armoured cables.<br />

2. For control cables : Multicore copper cable minimum 2.5 mm 2 with<br />

PVC insulation, armoured and PVC sheathed.<br />

3. Submersible Motor cable : According to Manufacturer<br />

The minimum size of control cable shall not be less than 2.5 mm 2 .<br />

All cables shall be suitably de-rated for grouping and higher ambient temperature.<br />

The cables shall conform for LT to IS:1554 - Part I and for HT to IS 1554 -<br />

Part - <strong>II</strong>., IS: 7098.<br />

GTS : General Technical Specification. Page 115