The HT Panel board for motors shall be capable to provide the following<br />

signals/data to the PLC for automation/visualization.<br />

■ Voltage on either side of the bus coupler, current for each outgoing feeder,<br />

energy consumed as well as incoming frequency.<br />

■ The HT panel board should be capable for switching on/off from local<br />

(pump house) or remote (i.e. from PLC via the MMI).<br />

■ Basic information of each breaker such as breaker on/off/trip, in test/service<br />

position etc. to be informed to PLC. PLC & MMI PC system is however<br />

outside the scope of this work.<br />

■ The auxiliary supply for tripping coil/closing coil (110V DC or 220V DC)<br />

shall be built-in power pack through rectifier unit and for spring charging<br />

motor of the VCB and that of the space heater, indication etc. of the panel,<br />

external 230V power shall be supplied for external source to the built-in<br />

wiring of the panel offered.<br />

Push button operated DOL starter :<br />

DOL starter shall be of double break type and shall incorporate air break contactor<br />

with bimetallic thermal electro magnetic overload relays on all three phases with<br />

start/stop push button in front of switch board. The starter shall be capable of<br />

10 operations per hour. The DOL starter shall conform to IS:13947 Part 4 – Sec 1<br />

(IEC 947-4-1 -1990).<br />

Star/Delta Starter:<br />

The push button operated Star Delta Starter shall be of the fully automatic type with<br />

an adjustable timer incorporated for automatic change-over from Star to Delta. The<br />

starter shall incorporate the electro magnetic or thermal type bimetallic overload<br />

releases, pneumatic electro time delay relay, the solenoid coil operated under<br />

voltage release and current operating single phasing preventor. The starter shall be<br />

capable of 10 operations per hour. The starter shall conform to IS:13947<br />

Part:4 Sec 1 (IEC 947-4-1 -1990).<br />

GTS : General Technical Specification. Page 112