Sharp and tight bends shall be avoided. Each wire shall be identified at both ends<br />

by ferrules indicating the designation of the wire in accordance with the<br />

schematic/wiring diagrams. The wire shall be terminated on the terminals of the<br />

relays, switches, instrument, conductors, lamps etc., or on the terminal blocks as the<br />

case may be. No joints shall be provided in between. Terminal blocks shall have<br />

screw type terminals which can take at least two wires per terminal on each side.<br />

At least 20% spare terminals shall be provided on each terminal block.<br />

Interlocking Arrangement:<br />

The panels containing the MCCB/MCB etc. shall be enclosed in free standing steel<br />

sheet enclosure with front cover so interlocked with the isolator that the door cannot<br />

be opened with isolator at ‘ON’ position.<br />

Inspection of Circuits:<br />

Facility for inspection of the circuits, to ascertain if all the conductors, relays, fuses,<br />

etc. are in proper working order/condition or otherwise shall be provided by means<br />

of a push button or selected switch.<br />

Labeling:<br />

Labels of switch gears shall indicate reference number of the switch, the specified<br />

current rating and the part of the distribution controlled. Labels on circuit breaker<br />

boards shall indicate the reference number of controlling switch. The lettering of all<br />

labels shall not be less than 5 mm, high. The schedule and details of the labels shall<br />

be submitted to the Engineer for approval.<br />

Cable entry:<br />

The cable entry shall preferably be from the bottom which shall be dust and vermin<br />

proof. The cable entry on each equipment shall be through a compression type<br />

cable gland. The cable gland plate shall be sufficiently strong to take the load of the<br />

cables and shall be mounted not less than 300 mm. above the floor level. The<br />

cables shall be suitably clamped before the cable gland to avoid any strain on it.<br />

GTS : General Technical Specification. Page 110