All spare contacts and terminal of panel mounted equipment and devices shall be<br />

wired to terminal blocks.<br />

At least 20% spare terminal shall be provided on each panel, uniformly distributed<br />

on all terminal blocks.<br />

Indicating Instruments :<br />

All electrical indicating instruments shall be digital square type of 144 sq.mm or<br />

96 sq.mm according to the suitability of panel. These shall be suitable for flush<br />

mounting with only flanges projecting on vertical panel. Instrument dial shall be<br />

white with black numericals and lettering.<br />

Instrument shall conform to IS:1248 and shall have accuracy class of 1.00 or better.<br />

The current coil of ammeters and potential coils of voltmeters shall continuously<br />

withstand 120% of rated current and voltage, respectively, without the loss of<br />

accuracy.<br />

The meters shall have external zero adjustments. The ammeters fitted in the motor<br />

circuits shall have suppressed scale to indicate the maximum starting current. The<br />

instrument shall be provided with glass cover to avoid the possibility of<br />

measurements due to static charge.<br />

The three phase three wire trivector meter shall comprise of kWh meter and kVARh<br />

meter mounted together with kVAh meter in one case with special summator<br />

mounted between them to register correct kVAh at all power factors.<br />

All the meters shall have respective maximum demand indicators to record the<br />

average power over a period of half an hour. The trivector meter shall conform to<br />

relevant IS.<br />

Equipment wiring :<br />

All the switch boards, panels, annunciator panel and mimic panel shall be neatly<br />

wired using 1100/660 volt grade PVC insulated stranded copper conductor cable of<br />

minimum 2.5 mm to suit the requirement. The wiring shall be bunched in groups<br />

by non-metallic clips or bands. Each group shall be adequately supported along its<br />

run to prevent sagging and strain on the terminals.<br />