Air Circuit Breakers:<br />

The medium voltage cubicle type switch board shall consist of four pole Air Circuit<br />

Breakers confirming to latest revision of IS:13947 Part 2/IEC:60947 Part 2. The<br />

breaker shall be manually draw out type in open execution with over current trip<br />

device adjustable 64% to 110%. Time setting for over load, adjustable current<br />

setting for short circuit protection and also earth fault protection adjustment facility<br />

shall be provided in the ACB.<br />

ACB shall be fitted with following :<br />

- Heavy duty switch having not less than 4 No. + 4NC contacts<br />

- Built in resin cast current transformer<br />

- Auxiliary contacts<br />

- Shunt and under voltage tripping device<br />

- Neutral CT for earth fault protection<br />

- The ACB shall be suitable for locking the breaker in various position. Provision<br />

for door locking ACB shall be provided with the requisite end termination<br />

lugs/sockets. Terminal bars for connecting more than one terminal.<br />

The ACB shall have breaking capacity not less than 35kA at 415V AC.<br />

Moulded case circuit breakers:<br />

Moulded Case Circuit Breakers confirming to latest revision of IS:13947<br />

Part 2/IEC:60947 Part 2 shall be fixed type fitted with trip free, manually closing<br />

mechanism, accommodated in a sheet steel housing of robust and vermin proof<br />

construction matching with switch boards. All MCCBs shall be tested as per<br />

IS-2516 Part-1, Sec-1 and shall be provided short circuit and overload protection.<br />

(position of the knob shall clearly indicate ON, OFF and TRIP conditions).<br />

Terminal Blocks:<br />

Terminal blocks shall be 650 V grade, 10 Amps., rated one piece moulded,<br />

complete with insulated barriers, screw type brass terminals suitable for stacking on<br />

C type rail and identification strips. Marking on the terminal strips shall correspond<br />

to wire numbers on the wiring diagrams. The terminal blocks for CT and VT<br />

secondary leads shall be provided with test links and isolating facilities. Also CT<br />

secondary leads shall be provided with short circuiting and earthing facilities.<br />

GTS : General Technical Specification. Page 108