15.4 Requirement of statutory authorities.<br />

The electrical equipment/installations shall comply with the requirements of<br />

Rules/Regulations as amended up-to-date, required by Statutory Acts or<br />

Authorities.<br />

- The Indian Electricity Rules, 1956<br />

- The Indian Electricity Act.<br />

- The Indian Electricity (Supply) Act, 1948<br />

- The requirements of Inspectorate of Electricity, Government of Meghalaya.<br />

15.5 Voltage regulation.<br />

During starting of heavy equipment the voltage may drop by a maximum of 15%<br />

for period of 45-60 seconds depending upon the duty of the driving equipment. All<br />

the electrical equipment shall, therefore, be suitable for trouble free and<br />

uninterrupted operation even during such voltage variation at the time of starting of<br />

heavy equipments.<br />

15.6 Frequency regulation.<br />

As experiences, frequency of power supply is highly fluctuating. Frequency dips as<br />

low as 47.50 Hz. and shoots as high as 51.50 Hz.. All plant and machineries are to<br />

be designed taking into consideration the highest fluctuating frequency of power<br />

supply.<br />

15.7 Ambient temperature.<br />

Where the equipment is installed outside and exposed to direct sunrays, these shall<br />

be suitable for operation at higher ambient temperature and rigorous weather<br />

conditions under which they are required to operate.<br />

15.8 Power factor.<br />

Suitable rating capacitors shall be provided to each individual motor above 1.5 KW<br />

rating along with discharge device of appropriate rating to improve the power factor<br />

above 0.95.<br />

GTS : General Technical Specification. Page 106