Version 4Q01: 12/01/01<br />

Attachment 4-Central Office<br />

Page 9<br />

removing any enclosure, together with all support structures (e.g., racking, conduits,<br />

power cables, etc.), at the termination of occupancy and restoring the grounds to their<br />

original condition.<br />

5. Use of Collocation Space<br />

5.1 Equipment Type. AT&T permits the collocation of any type of equipment necessary<br />

for interconnection to AT&T’s network or for access to AT&T’s unbundled network<br />

elements in the provision of telecommunications services, as the term "necessary" is<br />

defined by FCC 47 C.F.R. Section 51.323 (b). The primary purpose and function of<br />

any equipment collocated in a Premises must be for interconnection to AT&T's<br />

network or for access to AT&T's unbundled network elements in the provision of<br />

telecommunications services.<br />

5.1.1 Examples of equipment that would not be considered necessary include but are not<br />

limited to: Traditional circuit switching equipment, equipment used exclusively for<br />

call-related databases, computer servers used exclusively for providing information<br />

services, operations support system (OSS) equipment used to support CLEC network<br />

operations, equipment that generates customer orders, manages trouble tickets or<br />

inventory, or stores customer records in centralized databases, etc. AT&T will<br />

determine upon receipt of an application if the requested equipment is necessary based<br />

on the criteria established by the FCC. Multifunctional equipment placed on AT&T's<br />

Premises must not place any greater relative burden on AT&T's property than<br />

comparable single-function equipment. AT&T reserves the right to permit collocation<br />

of any equipment on a nondiscriminatory basis.<br />

5.1.2 Such equipment must at a minimum meet the following BellCore (Telcordia) Network<br />

Equipment Building Systems (NEBS) General Equipment Requirements: Criteria<br />

Level 1 requirements as outlined in the BellCore (Telcordia) Special Report SR-3580,<br />

Issue 1; equipment design spatial requirements per GR-63-CORE, Section 2; thermal<br />

heat dissipation per GR-063-CORE, Section 4, Criteria 77-79; acoustic noise per GR-<br />

063-CORE, Section 4, Criterion 128, and National Electric Code standards. Except<br />

where otherwise required by a Commission, AT&T shall comply with the applicable<br />

FCC rules relating to denial of collocation based on BHN’s failure to comply with this<br />

section.<br />

5.1.3 BHN shall not request more DS0, DS1, DS3 and optical terminations for a collocation<br />

arrangement than the total port or termination capacity of the equipment physically<br />

installed in the arrangement. The total capacity of the equipment collocated in the<br />

arrangement will include equipment contained in the application in question as well as<br />

equipment already placed in the arrangement. If full network termination capacity of<br />

the equipment being installed is not requested in the application, additional network<br />

terminations for the installed equipment will require the submission of another<br />

application. In the event that BHN submits an application for terminations that exceed<br />

CCCS 139 of 369