63 9810.0156 – Rev.04 –12/01/2007<br />

Installation / System<br />

The safety valve drainage line must be arranged<br />

when there is no pressure increase and during the time<br />

when safety valve operates. This line must not be<br />

installed against an open place; the drainage end must be<br />

open and tracable. The heating system water coming out at<br />

determined circumstances must be releasing without<br />

danger.<br />

Caution: <strong>Air</strong> release equipments must be placed<br />

to convenient points to release the air that will be<br />

occured during circulation and/or first filling<br />

application.<br />

If these equipments are not mounted to suitable<br />

places or/and equipments whose CE marker is not<br />

available are used, manufacturer company is not<br />

responsible for physical and sipiritual damages.<br />

Caution: The equipments and installation must<br />

be compatible with each other for working correctly<br />

and effectively. All of safety equipments which may<br />

directly effect the operation of boiler must be<br />

covenient with CE standards. If these equipments is<br />

not choosen or placed rightly, manufacturer company<br />

is not responsible for physical and sipiritual damages.<br />

The corrosion resistance of metal materiaI,used at<br />

hot water devices, depends on oxygen that is not exist in<br />

heating water. There will not be any damage after oxygen,<br />

mixed with first or addition water into the system, reacts<br />

with other materials. Transformation of water to black<br />

colour is a sign that there is no free waste oxygen in the<br />

system. Technical rules, especially VDI-Instruction 2035-2,<br />

suggest that heating system needs to be designed and<br />

operated in a way that oxygen inlet is not possible to<br />

heating water.<br />

At the floor heating systems, to prevent intransitive<br />

diffusion of oxygen to pass trough pipe walls, it is<br />

suggested to use plastic pipe which is convenable to DIN<br />

4726. For floor heating systems which is not resistant<br />

against oxygen,system separation must be done by an<br />

exchanger.<br />

33