FTA Manual.pdf - Industrial Air
FTA Manual.pdf - Industrial Air
FTA Manual.pdf - Industrial Air
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Installation<br />
3.6 Gas Blown Burners<br />
CAUTION! Use only fluid or gas fuel burner that<br />
is avaliable at CE norms. Burner ignition power must be<br />
set according to nominal heat efficiency of boiler.<br />
Please take care boiler mounting manual while<br />
installing boiler.<br />
Burners must be set according to nominal heat<br />
efficiency of boiler on low heat conditions. Power of 1st<br />
stage burner must be upper than 66% of boiler nominal<br />
power for two stage burner.<br />
Waste gas temperature value must not be lower<br />
than 160 °C for ordinary chimney.<br />
Height of chimney must be set properly for<br />
preventing condensation in chimney.<br />
Open the boiler cover and remove some rotarders<br />
from bottom pipes of front plate on required situation<br />
( Note : Number of removed rotarder must not<br />
exceed much more than 25% boiler pipes quantity. )<br />
Installation of suction limitation cover and<br />
additional air mechanism are recommended. Chimney<br />
must be avaliable for processof waste gas at two stage<br />
burner applications.<br />
Explosion cover setup of the boiler must not be<br />
changed and dont put any object to the front side of<br />
cover.<br />
3.7 Related demands for fuels that is used<br />
63 9810.0156 – Rev.04 –12/01/2007<br />
Fuels that is used must be convenable to<br />
defined norms. Otherwise; boiler will be out of<br />
guaranty conditions. Manufacturer company is not<br />
responsible for phisical or sipiritual damages.<br />
Coal gas , natural gas and LPG must be<br />
convenable to EN 437 norm or avaliable for local laws<br />
For fluid fues; Diesel fuel and fuel oil<br />
corresponding to DIN 51603 must be used<br />
Attention ! Fuel-oil and/or heavy oil fuels which is not<br />
in standards can not be used for boilers.<br />
Additive materials are recommended on conditions below<br />
- If they increase durability of fuel storage<br />
- If they increase termic resistance of fuel or reduce<br />
smell formation as tank is filled and provide the burning<br />
without sediment,<br />
Additive material causing sediment or ruin is<br />
forbidden<br />
Attention! It is not allowed to use fuel oil with<br />
Yakut/Elmas 6/8/10 series. Otherwise boiler will be out<br />
of warranty and manufacturer company is not<br />
responsible for physical and sipirutal damages.<br />
17