Checking Operations for CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS Master Units Section 6-2<br />

When an error occurs in a Slave, the Slave can be identified from the status of<br />

the Master’s indicators or from the status flags in the PLC’s Special I/O Unit<br />

Area.<br />

Error Probable cause Possible remedy<br />

The Master Unit’s<br />

RUN indicator is<br />

OFF<br />

The Master Unit’s<br />

RUN indicator is<br />

OFF<br />

The PLC’s power is OFF. Turn the PLC’s power supply ON.<br />

The same unit number has been set<br />

on another Special I/O Unit, causing<br />

an I/O UNIT OVER error in the PLC.<br />

The unit number has been set outside<br />

the specified range, causing an I/O<br />

UNIT OVER error in the PLC.<br />

A Special I/O Unit error occurred in<br />

the PLC because the usable node<br />

number setting was changed with the<br />

PLC power ON, but just the Master<br />

Unit was restarted.<br />

A Special I/O Unit error occurred in<br />

the PLC because the Master Unit is<br />

not connected securely.<br />

An input-output I/O table error<br />

occurred in the PLC because the Master<br />

Unit’s unit number or usable node<br />

number setting was changed after the<br />

I/O table was registered.<br />

Check that the same unit number is not used by more than<br />

one Special I/O Unit and restart the PLC. In particular, when<br />

the usable node number setting is IN0 to IN15 and OUT0 to<br />

OUT15, check that the next unit number after the one set on<br />

the Master Unit is not set on another Special I/O Unit.<br />

Check that the unit number is set within the range specified<br />

for Special I/O Units and restart the PLC.<br />

CS-series:<br />

Unit numbers 0 to F can be set when the maximum number<br />

of Slaves setting is 16 (pin 1 OFF); Mountable number of<br />

Master Units is 16 when using 10 words as a Special I/O<br />

Unit; Usable node number setting is IN0 to IN7 and OUT0 to<br />

OUT7<br />

Unit numbers 0 to E can be set when the maximum number<br />

of Slaves setting is 32 (pin 1 ON); Mountable number of Master<br />

Units is 8 when using 20 words as a Special I/O Unit;<br />

Usable node number setting is IN0 to IN15 and OUT0 to<br />

OUT15<br />

C200HX-CPU3@-(Z)E/-CPU4@-(Z)E, C200HX-CPU3@-(Z)E/<br />

-CPU4@-(Z)E, C200HE, and C200HS PLCs:<br />

Unit numbers 0 to 9 can be set when the maximum number<br />

of Slaves setting is 16 (pin 1 OFF); Mountable number of<br />

Master Units is 10 when using 10 words as a Special I/O<br />

Unit; Usable node number setting is IN0 to IN7 and OUT0 to<br />

OUT7<br />

Unit numbers 0 to 8 can be set when the maximum number<br />

of Slaves setting is 32 (pin 1 ON); Mountable number of Master<br />

Units is 5 when using 20 words as a Special I/O Unit;<br />

Usable node number setting is IN0 to IN15 and OUT0 to<br />

OUT15<br />

C200HX-CPU5@-(Z)E/-CPU6@-(Z)E/-CPU8@-(Z)E and<br />

C200HG-CPU5@-(Z)E/-CPU6@-(Z)E PLCs:<br />

Unit numbers 0 to 9 or A to F can be set when the maximum<br />

number of Slaves setting is 16 (pin 1 OFF); Mountable number<br />

of Master Units is 16 (when using 10 words as a Special<br />

I/O Unit; Usable node number setting is IN0 to IN7 and OUT0<br />

to OUT7<br />

Unit numbers 0 to 8 or A to E can be set when the maximum<br />

number of Slaves setting is 32 (pin 1 ON); Mountable number<br />

of Master Units is 8 (when using 20 words as a Special I/O<br />

Unit; Usable node number setting is IN0 to IN15 and OUT0 to<br />

OUT15<br />

Turn the PLC OFF and then ON again.<br />

Turn the PLC OFF, make sure that the Master Unit is<br />

mounted correctly, and then turn the PLC ON again. Replace<br />

the Master Unit if the error recurs.<br />

Register the I/O table again.<br />

The Master Unit is faulty. Replace the Master Unit.<br />