ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...
ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...
ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
3.6 Manual control<br />
This section describes the function in general for the <strong>ECL</strong> <strong>Comfort</strong><br />
<strong>210</strong> / <strong>310</strong> series. The shown displays are typical and not application<br />
related. They might differ from the displays in your application.<br />
It is possible to manually control the installed components.<br />
Manual control can only be selected in favorite displays in which<br />
the symbols for the controlled components (valve, pump etc.) are<br />
visible.<br />
Action: Purpose: Examples:<br />
Choose mode selector<br />
Confirm<br />
Choose manual mode<br />
Confirm<br />
Choose pump<br />
Confirm<br />
Switch ON the pump<br />
Switch OFF the pump.<br />
Confirm pump mode<br />
Choose motorized control valve<br />
Confirm<br />
Open the valve<br />
Stop opening the valve<br />
Close the valve<br />
Stop closing the valve<br />
Confirm valve mode<br />
To leave manual control, use the mode selector to select the<br />
desired mode. Push the dial.<br />
Manual control is typically used when commisioning the<br />
installation. The controlled components, valve, pump etc., can be<br />
controlled for correct function.<br />
Controlled components Circuit selector<br />
During manual operation, all control functions are deactivated. Frost<br />
protection is not active.<br />
When manual control is selected for one circuit, it is automatically<br />
selected for all circuits!<br />
98 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy