2.5.5 Electrical connections, Pt 1000 temperature sensors and signals<br />
<strong>A275</strong>:<br />
Terminal Sensor / description Type<br />
(recomm.)<br />
29 and 30 S1 Outdoor temperature sensor* ESMT<br />
28 and 30 S2 <strong>A275</strong>.3 only:<br />
Return temperature sensor,<br />
circuit 2<br />
27 and 30 S3 Boiler temperature sensor**,<br />
circuit 1<br />
26 and 30 S4 <strong>A275</strong>.3 only:<br />
Flow temperature sensor**,<br />
circuit 2<br />
25 and 30 S5 Return temperature sensor,<br />
circuit 1<br />
24 and 30 S6 <strong>A275</strong>.2 / <strong>A275</strong>.3 only:<br />
DHW tank temperature sensor,<br />
circuit 2 / 3<br />
23 and 30 S7 Room temperature sensor***,<br />
circuit 1<br />
22 and 30 S8 <strong>A275</strong>.3 only:<br />
Room temperature sensor***,<br />
circuit 2<br />
ESM-11 / ESMB /<br />
ESMC / ESMU<br />
ESMU / ESMB<br />
ESM-11 / ESMB /<br />
ESMC / ESMU<br />
ESM-11 / ESMB /<br />
ESMC / ESMU<br />
ESM-11 / ESMB /<br />
ESMC / ESMU<br />
ESM-10<br />
ESM-10<br />
* If the outdoor temperature sensor is not connected or the<br />
cable is short-circuited, the controller assumes that the<br />
outdoor temperature is 0 (zero) °C.<br />
** The boiler / flow temperature sensor must always be<br />
connected in order to have the desired functionality. If the<br />
sensor is not connected or the cable is short-circuited, the<br />
motorized control valve closes (safety function).<br />
*** Only for room temperature sensor connection. The room<br />
temperature signal can also be available from a Remote<br />
Control Unit (ECA 30 / 31). See 'Electrical connections, ECA<br />
30 / 31'.<br />
Factory established jumper:<br />
30 to common terminal.<br />
70 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy