<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
Alternative connection for P3 / M1, changeover valve:<br />
Application <strong>A375</strong>.2 / <strong>A375</strong>.3 (burner steps 3–6):<br />
Terminal Description Max. load<br />
48 Phase for burner B3<br />
47 B3 Burner ON / OFF 4 (2) A / 230 V a.c.*<br />
46 Not to be used<br />
45 Phase for burner B4<br />
44 B4 Burner ON / OFF 4 (2) A / 230 V a.c.*<br />
43 Not to be used<br />
42 Phase for burner B5<br />
41 B5 Burner ON / OFF 4 (2) A / 230 V a.c.*<br />
40 Phase for burner B6<br />
39 B6 Burner ON / OFF 4 (2) A / 230 V a.c.*<br />
* Relay contacts: 4 A for ohmic load, 2 A for inductive load<br />