<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
<strong>A375</strong>.1, example h<br />
Up to 8 x boiler ON / OFF control for a heating circuit. The first boiler (high efficiency) has highest priority.<br />
S1<br />
* = pressure relief valve<br />
B1 B2<br />
B8<br />
S5<br />
S3<br />
<strong>ECL</strong> <strong>310</strong><br />
+ ECA 32<br />
The first boiler can be a heat pump.<br />
The extension module ECA 32 is used to control boiler 5, 6, 7 and 8.<br />
Sequence for the boilers: Boiler 1, 2 - 3 - 4 - 5 - 6 - 7 - 8. Next day: Boiler 1, 3 - 4 - 5 - 6 - 7 - 8 - 2. Following day: Boiler 1, 4 - 5 - 6 - 7<br />
- 8 - 2 - 3 and so on.<br />
Burner steps are activated according to heat demand.<br />
The last burner step can be disabled if the outdoor temperaure is higher than a set value.<br />
Special settings for type <strong>A375</strong>.1, example h:<br />
P1<br />
Navigation: ID no.: Recommended setting:<br />
Heating circuit (circuit 1)<br />
Sequence type (code) for controlling the burners:<br />
MENU \ Settings \ Boiler: 'Sequence type' 11072 1<br />
Number of total burner steps:<br />
MENU \ Settings \ Boiler: ‘Steps' 11073 1 .... 8<br />
<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 39<br />