<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
<strong>A275</strong>.3, example g<br />
Boiler ON / OFF control for a direct heating circuit (1) and a mixing circuit (2).<br />
* = pressure relief valve<br />
S1<br />
B1<br />
Heating circuit 2 can alternatively be a floor heating circuit.<br />
Special settings for type <strong>A275</strong>.3, example g:<br />
S3<br />
S5<br />
M2<br />
P1<br />
<strong>ECL</strong> <strong>210</strong> / (<strong>310</strong>)<br />
S4<br />
S2<br />
P4<br />
*<br />
Navigation: ID no.: Recommended setting:<br />
Heating circuit (circuit 1)<br />
Circuit 1 must be able to receive a heat demand (desired flow temperature) from circuit 2:<br />
MENU \ Settings \ Application: 'Demand offset' 11017 3 K**<br />
** This value is added to the heat demand value from circuit 2<br />
Heating circuit (circuit 2)<br />
Circuit 2 must be able to send a heat demand (desired flow temperature) to circuit 1:<br />
MENU \ Settings \ Application: 'Send desired T' 12500 ON<br />
<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 31<br />