7.0 Settings, circuit 3<br />
7.1 Tank temperature<br />
Charge difference 13193<br />
Circuit Setting range Factory setting<br />
3 1 ... 50 K 15 K<br />
Number of degrees above the desired DHW temperature that will result in<br />
the desired boiler temperature for DHW heating.<br />
1... 50: Number of degrees to be added to the desired DHW<br />
temperature to obtain the desired boiler temperature<br />
for DHW heating.<br />
Start difference 13195<br />
Circuit Setting range Factory setting<br />
3 –50 ... –1 K –3 K<br />
Number of degrees below the desired DHW temperature that will start the<br />
DHW heating.<br />
-50 ... –1: Set the number of degrees.<br />
Temp.<br />
° C<br />
DHW heating<br />
Charge difference<br />
Stop difference<br />
Des. DHW temp.<br />
Start difference<br />
Actual DHW temp.<br />
Time<br />
The desired DHW temperature is related to the tank temperature<br />
sensor.<br />
Example:<br />
Desired DHW temp.: 55 °C<br />
Start difference: -3 K<br />
Result:<br />
The DHW heating starts when the temperature measured by the tank<br />
temperature sensor is lower than 52 °C.<br />
Temp.<br />
° C<br />
DHW heating<br />
Start difference<br />
Desired DHW temp.<br />
DHW temp.<br />
148 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy<br />
Time