ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...
ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...
ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
The heat curves represent the desired flow temperature at different outdoor temperatures and at a desired room temperature of 20 °C.<br />
120<br />
110<br />
100<br />
90<br />
80<br />
70<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
1.8<br />
1.4<br />
1.0<br />
0.6<br />
0.2<br />
2.2 2.6 3.0 3.4<br />
-30 -20 -10<br />
0 10 20<br />
The small arrows ( ) indicate 6 different outdoor temperature values at which you can change the heat curve.<br />
Temp. max. (flow temp. limit, max.) 12178<br />
Circuit Setting range Factory setting<br />
2 10 ... 150 °C 45 °C<br />
Choose the allowed max. flow temperature for your system.<br />
Adjust the factory setting, if required.<br />
Temp. min. (flow temp. limit, min.) 12177<br />
Circuit Setting range Factory setting<br />
2 10 ... 150 °C 10 °C<br />
Choose the allowed min. flow temperature for your system.<br />
Adjust the factory setting, if required.<br />
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.<br />
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.<br />
124 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy