<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
Infl. - min. (room temp. limitation, min.) 11183<br />
Circuit Setting range Factory setting<br />
1 0.0 .... 9.9 0.0<br />
Determines how much the desired flow temperature will be influenced<br />
(increased) if the actual room temperature is lower than the desired room<br />
temperature (P control).<br />
0.0: The room temperature has no influence.<br />
9.9: The room temperature has a big influence.<br />
Adapt. time (adaption time) 11015<br />
Circuit Setting range Factory setting<br />
1 OFF / 1 ... 50 s OFF<br />
Controls how fast the actual room temperature adapts to the desired room<br />
temperature (I control).<br />
OFF: The control function is not influenced by the 'Adapt.<br />
time'.<br />
1: The desired room temperature is adapted quickly.<br />
50: The desired room temperature is adapted slowly.<br />
The adaptation function can correct the desired flow temperature<br />
with max. 8 K x heat curve value.<br />
<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 107