The heat curves represent the desired flow temperature at different outdoor temperatures and at a desired room temperature of 20 °C.<br />
120<br />
110<br />
100<br />
90<br />
80<br />
70<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
1.8<br />
1.4<br />
1.0<br />
0.6<br />
0.2<br />
2.2 2.6 3.0 3.4<br />
-30 -20 -10<br />
0 10 20<br />
The small arrows ( ) indicate 6 different outdoor temperature values at which you can change the heat curve.<br />
Temp. max. (flow temp. limit, max.) 11178<br />
Circuit Setting range Factory setting<br />
1 10 ... 150 °C 90 °C<br />
Set the max. flow temperature for the system. The desired flow<br />
temperature will not be higher than this setting. Adjust the factory<br />
setting, if required.<br />
Temp. min. (flow temp. limit, min.) 11177<br />
Circuit Setting range Factory setting<br />
1 10 ... 150 °C 10 °C<br />
Set the min. flow temperature for the system. The desired flow<br />
temperature will not be lower than this setting. Adjust the factory<br />
setting, if required.<br />
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.<br />
‘Temp. min.’ is overruled if 'Total stop' is active in Saving mode or<br />
'Cut-out' is active.<br />
‘Temp. min.’ can be overruled by the influence from the return<br />
temperature limitation (see 'Priority').<br />
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.<br />
104 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy