<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
Setting ID Page Factory settings in circuit(s)<br />
Ext. input (external override), <strong>ECL</strong> <strong>210</strong> 11141 121 OFF<br />
1 2 3<br />
Ext. input (external override) — <strong>ECL</strong> <strong>310</strong> 11141 122 OFF<br />
Ext. mode (external override mode) 11142 122<br />
COM-<br />
FORT<br />
Heat curve 123 1.0<br />
Temp. max. (flow temp. limit, max.) 12178 124 45 °C<br />
Temp. min. (flow temp. limit, min.) 12177 124 10 °C<br />
Charge difference 12193 125 15 K<br />
Start difference 12195 125 –3 K<br />
Stop difference 12194 126 3 K<br />
Infl. - max. (room temp. limitation, max.) 12182 127 -4.0<br />
Infl. - min. (room temp. limitation, min.) 12183 128 0.0<br />
Adapt. time (adaption time) 12015 128 OFF<br />
High T out X1 (return temp. limitation, high limit, X-axis) 12031 129 15 °C<br />
Low limit Y1 (return temp. limitation, low limit, Y-axis) 12032 129 40 °C<br />
Low T out X2 (return temp. limitation, low limit, X-axis) 12033 129 -15 °C<br />
High limit Y2 (return temp. limitation, high limit, Y-axis) 12034 130 60 °C<br />
Infl. - max. (return temp. limitation - max. influence) 12035 130 0.0<br />
Infl. - min. (return temp. limitation - min. influence) 12036 130 0.0<br />
Adapt. time (adaptation time) 12037 130 25 s<br />
Priority (priority for return temp. limitation) 12085 131 OFF<br />
Auto saving (saving temp. dependent on outdoor temp.) 12011 132 -15 °C<br />
Boost 12012 132 OFF<br />
Ramp (reference ramping) 12013 133 OFF<br />
Optimizer (optimizing time constant) 12014 133 OFF<br />
Pre-stop (optimized stop time) 12026 134 ON<br />
Based on (optimization based on room / outdoor temp.) 12020 134 OUT<br />
Total stop 12021 134 OFF<br />
Cut-out (limit for heating cut-out) 12179 135 20 °C<br />
Motor pr. (motor protection) 12174 136 OFF<br />
Xp (proportional band) 12184 136 80 K<br />
Tn (integration time constant) 12185 136 30 s<br />
M run (running time of the motorized control valve) 12186 136 50 s<br />
Nz (neutral zone) 12187 137 3 K<br />
Min. act. time (min. activation time gear motor) 12189 137 10<br />
ECA addr. (choice of Remote Control Unit) 12010 139 OFF<br />
Ch.-o. valve / P (changeover valve / pump) 12051 139 ON<br />
Tank, sec. / prim. 12053 139 OFF<br />
Circ. P priority 12055 139 OFF<br />
DHW P post-run 12041 140 0 m<br />
Send desired T 12500 140 ON<br />
P exercise (pump exercise) 12022 140 ON<br />
M exercise (valve exercise) 12023 140 OFF<br />
DHW priority (closed valve / normal operation) 12052 141 OFF<br />
P frost T 12077 141 2 °C<br />
<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 101