<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
4.0 Settings overview<br />
It is recommendable to make a note of any changed settings in the empty columns.<br />
Setting ID Page Factory settings in circuit(s)<br />
Heat curve 103 1.0<br />
Temp. max. (flow temp. limit, max.) 11178 104 90 °C<br />
Temp. min. (flow temp. limit, min.) 11177 104 10 °C<br />
Ext. desired T — (<strong>ECL</strong> <strong>Comfort</strong> <strong>310</strong>) 105<br />
Infl. - max. (room temp. limitation, max.) 11182 106 -4.0<br />
Infl. - min. (room temp. limitation, min.) 11183 107 0.0<br />
Adapt. time (adaption time) 11015 107 OFF<br />
High T out X1 (return temp. limitation, high limit, X-axis) 11031 108 15 °C<br />
Low limit Y1 (return temp. limitation, low limit, Y-axis) 11032 108 40 °C<br />
Low T out X2 (return temp. limitation, low limit, X-axis) 11033 108 -15 °C<br />
High limit Y2 (return temp. limitation, high limit, Y-axis) 11034 109 60 °C<br />
Infl. - max. (return temp. limitation - max. influence) 11035 109 0.0<br />
Infl. - min. (return temp. limitation - min. influence) 11036 109 0.0<br />
Adapt. time (adaptation time) 11037 109 25 s<br />
Priority (priority for return temp. limitation) 11085 110 OFF<br />
Auto saving (saving temp. dependent on outdoor temp.) 11011 111 -15 °C<br />
Boost 11012 111 OFF<br />
Optimizer (optimizing time constant) 11014 112 OFF<br />
Pre-stop (optimized stop time) 11026 112 ON<br />
Based on (optimization based on room / outdoor temp.) 11020 113 OUT<br />
Total stop 11021 113 OFF<br />
Cut-out (limit for heating cut-out) 11179 113 20 °C<br />
Difference 11046 114 8 K<br />
Max. T limit 11049 114 90 °C<br />
Min. ON time 11071 114 0 m<br />
Sequence type (<strong>A375</strong> applications) 11072 115 3<br />
Stop at T out 11038 115 OFF<br />
Protection 11047 116 OFF<br />
Band limit (<strong>A375</strong> applications) 11048 116 20 K<br />
Reaction, o. band (outside band) (<strong>A375</strong> applications) 11074 117 60 s<br />
Reaction, in band (<strong>A375</strong> applications) 11075 118 120 s<br />
Steps (<strong>A375</strong> applications) 11073 118 1<br />
ECA addr. (choice of Remote Control Unit) 11010 119 OFF<br />
Demand offset 11017 119 OFF<br />
P demand 11050 119 OFF<br />
Send desired T 11500 119 OFF<br />
P exercise (pump exercise) 11022 120 ON<br />
P frost T 11077 120 2 °C<br />
P heat T (heat demand) 11078 120 20 °C<br />
P post-run 11040 120 3 m<br />
Frost pr. T (frost protection temperature) 11093 120 10 °C<br />
1 2 3<br />
100 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy