68-0133 - Y8610U Intermittent Pilot Retrofit Kit - Air & Water
68-0133 - Y8610U Intermittent Pilot Retrofit Kit - Air & Water
68-0133 - Y8610U Intermittent Pilot Retrofit Kit - Air & Water
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Y8610U</strong> INTERMITTENT PILOT RETROFIT KIT<br />
SPECIFICATIONS<br />
IMPORTANT<br />
The specifications given in this publication do not<br />
include normal manufacturing tolerances. Therefore,<br />
units might not match the listed specifications<br />
exactly. Also, units are tested and calibrated under<br />
closely controlled conditions, and some minor<br />
differences in performance can be expected if those<br />
conditions are changed.<br />
SUPER TRADELINE® Models<br />
SUPER TRADELINE® models are selected and packaged for<br />
ease of handling, ease of stocking, and maximum replacement<br />
value. SUPER TRADELINE® model specifications are the<br />
same as those of standard models, except as noted.<br />
SUPER TRADELINE® Model Available:<br />
<strong>Y8610U</strong> <strong>Intermittent</strong> <strong>Pilot</strong> <strong>Retrofit</strong> <strong>Kit</strong>:<br />
• Meets ANSI Z21.71 Automatic <strong>Intermittent</strong> <strong>Pilot</strong> Ignition<br />
Systems for Field Installation.<br />
• For natural or LP gas applications.<br />
• 90 second maximum ignition trial, shuts off, waits six<br />
minutes nominal, then reinitiates the pilot ignition<br />
sequence. The ignition trial, shutoff, and wait cycle<br />
repeats until the pilot lights or the call for heat ends.<br />
100 percent pilot shutoff on loss of flame.<br />
• S8610U <strong>Intermittent</strong> <strong>Pilot</strong> Module.<br />
• VR8304M Dual Valve Combination Gas Control.<br />
• Refer to Fig. 1 for other components.<br />
Ambient Temperature Rating:<br />
VR8304M: -40°F to 175°F (-40°C to 79°C).<br />
S8610U: -40°F to 165°F (-40°C to 74°C). (If main valve<br />
current is 1A or less, 175°F (79°C) maximum<br />
ambient applies.)<br />
Also refer to Igniter-Sensor specifications.<br />
Electrical Ratings:<br />
Voltage and Frequency: 20.5 to 28.5 Vac (24 Vac<br />
nominal), 60 Hz.<br />
Current Rating: 0.7A (includes both module and<br />
gas control).<br />
Thermostat Anticipator Setting: 0.7A plus current ratings of<br />
other devices in the thermostat control circuit.<br />
Relative Humidity Rating:<br />
5 to 90 percent at 95°F (35°C).<br />
ORDERING INFORMATION<br />
For ordering information when purchasing replacement and modernization products from your TRADELINE® wholesaler or your<br />
distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number, or specify:<br />
1. SUPER TRADELINE® order number.<br />
If you have additional questions, need further information, or want to comment on our products or services, please write or<br />
phone:<br />
1. Your local Honeywell Home and Building Control sales office (check white pages of phone directory).<br />
2. Home and Building Control Customer Logistics<br />
Honeywell Inc.,<br />
1885 Douglas Drive North<br />
Minneapolis, Minnesota 55422-4386<br />
In Canada—Honeywell Limited/Honeywell Limitee, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.<br />
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,<br />
Germanuy, Japan, Mexicco, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.<br />
<strong>68</strong>-<strong>0133</strong>—2<br />
2<br />
Thermostat Compatibility:<br />
Compatible with any Honeywell 24V thermostat and with<br />
competitive 24V thermostats that are powered independently<br />
of the module.<br />
Transformer Sizing:<br />
Add current ratings of Y8610, vent damper, and any other<br />
control system components. Multiply this total by 24V to<br />
determine the transformer VA requirement.<br />
Wiring Connections:<br />
Between the module and gas control: 30 in. (762 mm)<br />
wiring harness with 1/4 in. quick-connect terminals.<br />
Between the module and the igniter-sensor: 30 in.<br />
(762 mm) ignition cable with stud terminal and 1/4 in.<br />
quick-connect terminal.<br />
<strong>Intermittent</strong> <strong>Pilot</strong> Module Specifications:<br />
S8610U <strong>Intermittent</strong> <strong>Pilot</strong> Module, for natural or LP gas<br />
applications only.<br />
Dimensions:<br />
See Fig. 2.<br />
Flame Failure Response Time:<br />
0.8 second maximum at 1.0 uA flame current.<br />
Ignition Timing:<br />
Provides a 90 second maximum ignition trial, shuts off, waits<br />
six minutes nominal, then reinitiates the pilot ignition<br />
sequence. The ignition trial, shutoff, wait cycle repeats until<br />
the pilot lights or the call for heat ends. During the shutoff<br />
sequence, gas is shut off 100 percent.<br />
Mounting:<br />
Mounts in any position except with terminals up.<br />
Recommended mounting position is with terminals down to<br />
provide maximum protection from dripping water or dust<br />
accumulation. Fasten with No. 6-32 machine screws or No. 8<br />
sheet metal screws of appropriate length. Refer to Fig. 12.<br />
Spark Generator Output:<br />
13 kV peak at 25 pF load (16 kV peak open circuit).<br />
Terminals:<br />
1/4 in. male quick-connects. S8610U has Molex plug for<br />
connection to Honeywell D80D Vent Damper. Once the<br />
S8610U has powered a vent damper, the module works only<br />
if the vent damper is connected.