420010264101 <strong>GHO</strong> - TRON 5.5000 / 5.5800 R<br />

Ref. Description<br />

t1 Duration Waiting time for confirmation<br />

of air pressure<br />

t2 Preventilation time<br />

t3 Safety time<br />

t4 Pressurizing time<br />

t5 Time for enabling operation of the<br />

main gas valve on minimum capacity<br />

t6 Time for enabling operation of the<br />

main gas valve on maximum capacity<br />

The control box starts the burner<br />

fan, to carry out the prepurging of<br />

the combustion chamber, and<br />

cheks the vent air pressure through<br />

the air pressure switch. At the<br />

end of prepurging, the ignition<br />

transformer cuts-in and generates<br />

a spark between the electrodes. At<br />

the same time the two gas valves<br />

LANDIS & STAEFA, Model LFL1.333 OPERATING CYCLE<br />

Duration<br />

8”<br />

36”<br />

2”<br />

4”<br />

10”<br />

10”<br />

t1 t2<br />

Pressostato Gas manostat gas<br />

Motore Fan ventilatore motor<br />

Pressostato Air Switch aria<br />

Trasformatore<br />

Ignition di transformer<br />

accensione<br />

Valvola Gas valve gas<br />

Consenso<br />

min./max. Min/max capacity potenza<br />

enabling device<br />

100%<br />

Serranda aria min<br />

Air damper 0<br />

Serranda Gas damper gas<br />

Flame Rivelazione detector<br />

di fiamma<br />

Cut-out Spia pilot di blocco lamp<br />

Ciclo Normal di funzionamento operating normale cycle<br />

open (Vs safety valve and Vl working valve). The total safety, in case of missed ignition or casual burner's flame-out, is<br />

granted by a ionisation probe which cuts-in and sets the burner shutdown within the safety time. In case of gas lack or a<br />

major pressure drop, the minimum air pressure switch shuts down the burner.<br />

t4<br />

4<br />

t5<br />

t3<br />

t6<br />

Operating Ciclo di cycle funzionamento in the event of<br />

ignition in mancanza failureNormal di fiamma operating all'accensione cycle<br />

t1 t2<br />

t3<br />

LANDIS & STAEFA SQM 50.481A2 AIR DAMPER MOTOR<br />

Remove cover to gain access to the adjusting cams.The cams are to be adjusted through the suitable key provided for.<br />

Description:<br />

Manual change<br />

I - High flame operating opening position adjusting cam (Heavy-Oil /Gas).<br />

II - Limit switch for the air damper position at burner’s shut down.<br />

III - Ignition flame opening position adjusting cam (Gas).<br />

IV - Ignition flame opening position adjusting cam(Heavy-Oil).<br />

V - Low flame operating opening position adjusting cam (Gas).<br />

VI - Low flame operating opening position adjusting cam (Heavy-Oil).<br />

VII - Not used cam.<br />

VIII - Not used cam.<br />

t4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!