7.0 Difficulty<br />

7.2 Replacing the battery<br />

You can expect to receive 3 to 6 years of service life from the UPS's battery when<br />

installed in a cool, dry location. If you suspect the battery is weak, allow the UPS<br />

to charge the battery for at least 6 hours and perform the Test for proper<br />

operation described in section 3.7. If after repeating the test you find that the run<br />

time is still too short, follow the procedures below to replace the battery.<br />

Note: Please read the cautions at the beginning of this section.<br />

7.2.1 Turn off the UPS and unplug it from service. Lay the UPS on its left side and<br />

remove the two battery door screws. Remove only the screws indicated on the<br />

battery door.<br />

7.2.2 Gently pull out the battery by grasping the white tab.<br />

7.2.3 Remove the two wires connecting the battery to the UPS. To loosen the wire<br />

connectors, gently wiggle the connectors side-to-side while pulling straight back<br />

from the mating battery connector.<br />

7.2.4 Connect the battery wires to the new battery. The red wire is positive (+), the<br />

black wire is negative (-).<br />

7.2.5 Position the new battery as shown below and place it into the UPS. Arrange<br />

the wires so that they will not interfere with the battery installation.<br />

7.2.6 Close the battery door and fasten the two battery door screws.<br />

7.2.7 Return the worn battery to the factory for recycling.<br />