Safety Features<br />

Typical lab floor<br />

• Recessed safety shower heads<br />

were installed without an<br />

escutcheon. Monthly testing<br />

damages the adjacent dry wall,<br />

peels & becomes a breeding<br />

ground for mold growth.<br />

• HDR CUH2A coordinated a<br />

site visit by Water Saver &<br />

provided a mock-up for the<br />

correct installation for EH&S to<br />

review. Water Saver provided<br />

<strong>UCSF</strong> with additional<br />

escutcheons for installation.<br />