It is recognized that the fire protection system design relates to the risk of property loss, injury,<br />

and environmental emissions. As such, the following parties will be consulted regarding the fire<br />

protection system:<br />

State Fire Marshall.<br />

NDEP.<br />

The key elements of the system proposed for each area of the facility are presented in Table 1.5-<br />

3 below.<br />

Area Description<br />

Table 1.5-3: Proposed Fire Protection/Detection Systems<br />

Fire Extinguishers<br />

Class A/B/C 1<br />

Fire Extinguishers<br />

Class C 2<br />

PMR <strong>RCRA</strong> <strong>Permit</strong> <strong>Application</strong>, <strong>Dry</strong> <strong>Hills</strong> Facility Page 47<br />

JBR Environmental Consultants, Inc. | HATCH March 2013<br />

Fire Alarm System<br />

Automatic<br />

Sprinkler System<br />

Automatic Clean<br />

Agent Suppression<br />

System 3<br />

Hydrant Coverage<br />

Fire Water<br />

Containment<br />

Gravel Bed (Fire<br />

Spread Resistance)<br />

The Proposed TSF Building – General X X X X X X X X<br />

Electrical Room (MCC)<br />

X X<br />

X<br />

Control Room<br />

X X X 5<br />

Laboratory Area X<br />

X X<br />

Process Area X<br />

X X<br />

Clean Storage and Maintenance Area X<br />

X X<br />

Office Area X<br />

X X<br />

The Area of the Utility Building X<br />

X X X X<br />

X<br />

Utility Building X<br />

X X<br />

Diesel Storage and Power Generation X<br />

X<br />

X 4<br />

NOTES:<br />

1. Class A/B/C Fire Extinguishers are all purpose fire extinguishers used to fight ordinary combustible (Class A),<br />

flammable / combustible liquid (Class B), and energized electrical equipment (Class C) fires. Extinguishers<br />

will be in accordance with NFPA 10.<br />

2. Class C Fire Extinguishers are those intended for use on Energized Electrical Equipment fires only.<br />

Extinguishers will be in accordance with NFPA 10.<br />

3. A clean agent suppression system refers to extinguishants which vaporize readily and leave no residue. They<br />

are designed to extinguish a fire by displacing oxygen, reducing heat, or interrupting chemical reactions (ex.<br />

FM-200 or Ecaro-25). These systems are to be supplied by an approved vendor and will be in accordance with<br />

NFPA 2001.<br />

4. Generators to include independent clean agent suppression systems. To be supplied by vendor and will be in<br />

accordance with NFPA 2001.