Insulation The following insulation values will be provided in the building of the proposed TSF: Roof R = 20 Walls R = 13 Walls Below Grade R = 7.5 Unheated Slabs R = 10 Note: R-value is a measure of insulation resistivity. Secondary Partitions Secondary partitions within the storage area will be insulated sheet metal wall panels. The wall height will be from floor to the bottom chord of the roof trusses. All joints will be sealed with flexible seal materials and finished with an epoxy coating. The surfaces will be coated with epoxy enamel. Secondary partitions within the office/washrooms areas will be concrete wall and sealed with epoxy coating. Personnel Doors Exterior and interior personnel doors within the facility will be constructed of a pressed steel frame and a door, both coated with epoxy enamel. A glazed panel will be inset at eye level wherever practical and necessary. The industrial doors throughout the building are described below. Exterior over-head doors Structural steel channel frame coated with epoxy enamel. Insulated, hurricane resistant roll-up metal sectional door coated with epoxy enamel. Motorized. Weather sealed. Safety reversing edges. Interior Roll-up Doors Structural steel channel frame coated with epoxy enamel. Metal door coated with epoxy enamel. Motorized. Safety reversing edges. PMR RCRA Permit Application, Dry Hills Facility Page 8 JBR Environmental Consultants, Inc. | HATCH March 2013
Fire Doors/Emergency Exit Doors Pressed steel frame and doors with UL fire resistance rating with glazed panel at eye level. Motorized roll-up curtain door coated with epoxy enamel and with steel slats and fusible links. Door Glazed Panels Hardware Windows Fire doors/Emergency exit doors: 6 millimeters (mm) thick, wired clear glazing with steel wire mesh 13 mm on center for fire rated doors. Interior doors: 6 mm thick, clear tempered glass Hardware, including panic hardware, for both interior/exterior personnel doors will be extra heavy-duty, industrial type. Key system will be based on a grand master, sub-master, and individual areas as required by industry standards. Exterior Windows: steel industrial frame with opening section, double-glazed units with paint finish. Interior Windows: steel industrial frame with sliding section and single-glazed units with paint finish. Floor Finishes Concrete floors in all process and storage areas: coated with epoxy enamel. Clean and dirty locker rooms, washrooms, janitors’ room, laundry room, and lunch room: non-slip ceramic or quarry tile. Offices and entrance lobby: sheet vinyl or vinyl composite tile. Concrete floors in service rooms: coated with epoxy enamel. Wall Finishes Concrete walls in all process and storage areas: coated with epoxy enamel. Offices and entrance lobby: painted concrete. Clean and dirty locker rooms, washrooms: ceramic tile on concrete walls. PMR RCRA Permit Application, Dry Hills Facility Page 9 JBR Environmental Consultants, Inc. | HATCH March 2013
- Page 9 and 10: PMR Nevada RCRA Permit Application
- Page 11 and 12: ITEM # REGULATIONS GENERAL DESCRIPT
- Page 13 and 14: ITEM # REGULATIONS GENERAL DESCRIPT
- Page 15 and 16: ITEM # REGULATIONS GENERAL DESCRIPT
- Page 17 and 18: ITEM # REGULATIONS GENERAL DESCRIPT
- Page 19 and 20: M-3 M-3 ITEM # REGULATIONS GENERAL
- Page 21 and 22: OMB# 2050-0024; Expires ___________
- Page 23 and 24: EPA ID Number OMB#: 2050-0024; Expi
- Page 25 and 26: EPA ID Number ADDENDUM TO THE SITE
- Page 27 and 28: EPA ID Number OMB#: 2050-0024; Expi
- Page 29 and 30: EPA ID Number OMB#: 2050-0024; Expi
- Page 31 and 32: EPA ID Number OMB#: 2050-0024; Expi
- Page 33 and 34: This document is for reference purp
- Page 35 and 36: A B C D E F $$W ATERMARKD$$ N 4,475
- Page 37 and 38: Precious Metals Recovery LLC Dry Hi
- Page 39 and 40: 3.2 Barrier and Means to Control En
- Page 41 and 42: 19.0 APPROVAL OF PETITION FOR EXTEN
- Page 43 and 44: LIST OF TABLES Table 1.2-1 Secondar
- Page 45 and 46: Figure 23.1-1 Decomposition & Waste
- Page 47 and 48: Section 10 Appendices 10-A Figures
- Page 49 and 50: HVAC Heating, Ventilation, and Air
- Page 51 and 52: GLOSSARY OF SELECTED TERMS [Authori
- Page 53 and 54: INTRODUCTION Precious Metals Recove
- Page 55 and 56: Pre-application Public Meeting - 40
- Page 57 and 58: (Purity ≥ 99.5%, Directly Stored)
- Page 59: Administration (MSHA) document, Con
- Page 63 and 64: When leaving the plant spaces, work
- Page 65 and 66: Infiltration Air Office Area Pig Pi
- Page 67 and 68: personnel will be trained in respon
- Page 69 and 70: Figure 1.2-1: Elemental Mercury Tra
- Page 71 and 72: Tanks Or Containers Carbon Drums (n
- Page 73 and 74: Figure 1.2-2: Calomel Feed Preparat
- Page 75 and 76: Figure 1.2-3: Filter Press and Loca
- Page 77 and 78: Activated carbon is used in the air
- Page 79 and 80: Figure 1.2-5: SO2 Scrubber and Loca
- Page 81 and 82: Above the retort tray/drum transfer
- Page 83 and 84: Figure 1.2-8: Carbon Filter and Loc
- Page 85 and 86: Figure 1.2-10: Overall Ventilation
- Page 87 and 88: Wash water from open sumps. Safety
- Page 89 and 90: 1.3 Elemental Mercury Storage - 40
- Page 91 and 92: The following items are located out
- Page 93 and 94: Control System Architecture The pla
- Page 95 and 96: will be supplied in accordance with
- Page 97 and 98: Outdoor Material Storage A list of
- Page 99 and 100: It is recognized that the fire prot
- Page 101 and 102: Outdoor Areas Hydrants and hose bo
- Page 103 and 104: the event of a security violation,
- Page 105 and 106: 2.3 Determination of Treatment Para
- Page 107 and 108: Table 2.5-2: Test Methods Parameter
- Page 109 and 110: Sampling Containerized Waste The te
Fire Doors/Emergency Exit Doors<br />
Pressed steel frame and doors with UL fire resistance rating with glazed panel at eye<br />
level.<br />
Motorized roll-up curtain door coated with epoxy enamel and with steel slats and<br />
fusible links.<br />
Door Glazed Panels<br />
Hardware<br />
Windows<br />
Fire doors/Emergency exit doors: 6 millimeters (mm) thick, wired clear glazing with<br />
steel wire mesh 13 mm on center for fire rated doors.<br />
Interior doors: 6 mm thick, clear tempered glass<br />
Hardware, including panic hardware, for both interior/exterior personnel doors will be<br />
extra heavy-duty, industrial type.<br />
Key system will be based on a grand master, sub-master, and individual areas as<br />
required by industry standards.<br />
Exterior Windows: steel industrial frame with opening section, double-glazed units<br />
with paint finish.<br />
Interior Windows: steel industrial frame with sliding section and single-glazed units<br />
with paint finish.<br />
Floor Finishes<br />
Concrete floors in all process and storage areas: coated with epoxy enamel.<br />
Clean and dirty locker rooms, washrooms, janitors’ room, laundry room, and lunch<br />
room: non-slip ceramic or quarry tile.<br />
Offices and entrance lobby: sheet vinyl or vinyl composite tile.<br />
Concrete floors in service rooms: coated with epoxy enamel.<br />
Wall Finishes<br />
Concrete walls in all process and storage areas: coated with epoxy enamel.<br />
Offices and entrance lobby: painted concrete.<br />
Clean and dirty locker rooms, washrooms: ceramic tile on concrete walls.<br />
PMR <strong>RCRA</strong> <strong>Permit</strong> <strong>Application</strong>, <strong>Dry</strong> <strong>Hills</strong> Facility Page 9<br />