Precious Metals Recovery LLC RCRA Permit Application Dry Hills ...
Precious Metals Recovery LLC RCRA Permit Application Dry Hills ... Precious Metals Recovery LLC RCRA Permit Application Dry Hills ...
Fire Detection and Control Systems Where a fire alarm system is listed in Table 1.5-3, the system will typically include smoke detectors, heat detectors, and/or manual fire pull stations. The fire protection system will also include the following elements: Audible and visual alarms. Automated controls. o All fire alarm control panels will be supplied by two independent connections from the power supply. o Control system will automatically notify appropriate emergency response. (See Appendix 6-A). Fire water level and flow detection. Instrumentation will monitor the level of water in the fire water tank as well as the flow of water. Proposed TSF Building Fire extinguishers will be installed throughout the proposed TSF (including the office, electrical room, and plant spaces). Sprinklers will be installed to service all areas of the building except the electrical room. The system will be supplied by a fire water pump and reservoir external to the proposed TSF. The Hygiene Dust Collector will be equipped with a sprinkler system and explosion panels. Utility Building Adequate freeze protection will be provided in the fire water supply tank, pumps, and piping. In addition, the following elements of fire protection are included in the design: Fire extinguishers will be installed throughout the Utility Building. Independent detection/suppression systems will be provided with the diesel generator units. A one hour fire suppression wall (Fire Wall) is designed to separate the fire water pump room as per NFPA 20 4.12.1.1. PMR RCRA Permit Application, Dry Hills Facility Page 48 JBR Environmental Consultants, Inc. | HATCH March 2013
Outdoor Areas Hydrants and hose boxes will be located around the perimeter of the proposed TSF compound allowing for emergency response access. A 100-foot fire apron will encompass the proposed TSF compound with noncombustible ground cover. Fire Water Supply and Distribution The Fire Water Tank (1542-TK-020) has a live capacity of 240,000 gallons. This capacity is based on the following assumptions: Discharge flow rate of 2,000 GPM (Includes 33% contingency on the minimum flow requirements of IFC-2012 B105.2). Minimum two hour duration as per NFPA 122-2010 13.7.2 and IFC-2012 Table B105 with fire wall separation areas. The fire water tank will be located near the Utility Building. A description of the tank is provided below: o Concrete construction coated with epoxy enamel. o Located on grade west of the Utility Building. o Membrane in foundation impermeable to water. o Rectangular configuration (81 feet long by 63 feet wide by 15 feet deep). o Freeze protection will be provided. o Equipped with two, 2,000 GPM, vertical turbine pumps (one electric and one diesel) and an electric jockey pump to maintain pressure in the fire water supply piping. 1.5.6 Effluent Treatment and Disposal Systems The Sanitary Wastewater System is designed to be separate from other regulated waste streams from the proposed TSF. This sanitary wastewater will flow into a Sanitary Wastewater Collection Tank. The Sanitary Wastewater Collection Tank will have approximately two weeks of storage. Effluent from the Sanitary Wastewater Collection Tank will be managed in accordance with applicable regulations. For preliminary design purposes, the proposed TSF contemplates the Sanitary Wastewater Collection Tank will be intermittently emptied by vacuum truck for off-site treatment and disposal (see Appendix 1-C). Other alternatives, such as an in-ground septic system, or an off-site leach field may be considered, but are beyond the scope of this application. PMR RCRA Permit Application, Dry Hills Facility Page 49 JBR Environmental Consultants, Inc. | HATCH March 2013
- Page 49 and 50: HVAC Heating, Ventilation, and Air
- Page 51 and 52: GLOSSARY OF SELECTED TERMS [Authori
- Page 53 and 54: INTRODUCTION Precious Metals Recove
- Page 55 and 56: Pre-application Public Meeting - 40
- Page 57 and 58: (Purity ≥ 99.5%, Directly Stored)
- Page 59 and 60: Administration (MSHA) document, Con
- Page 61 and 62: Fire Doors/Emergency Exit Doors Pr
- Page 63 and 64: When leaving the plant spaces, work
- Page 65 and 66: Infiltration Air Office Area Pig Pi
- Page 67 and 68: personnel will be trained in respon
- Page 69 and 70: Figure 1.2-1: Elemental Mercury Tra
- Page 71 and 72: Tanks Or Containers Carbon Drums (n
- Page 73 and 74: Figure 1.2-2: Calomel Feed Preparat
- Page 75 and 76: Figure 1.2-3: Filter Press and Loca
- Page 77 and 78: Activated carbon is used in the air
- Page 79 and 80: Figure 1.2-5: SO2 Scrubber and Loca
- Page 81 and 82: Above the retort tray/drum transfer
- Page 83 and 84: Figure 1.2-8: Carbon Filter and Loc
- Page 85 and 86: Figure 1.2-10: Overall Ventilation
- Page 87 and 88: Wash water from open sumps. Safety
- Page 89 and 90: 1.3 Elemental Mercury Storage - 40
- Page 91 and 92: The following items are located out
- Page 93 and 94: Control System Architecture The pla
- Page 95 and 96: will be supplied in accordance with
- Page 97 and 98: Outdoor Material Storage A list of
- Page 99: It is recognized that the fire prot
- Page 103 and 104: the event of a security violation,
- Page 105 and 106: 2.3 Determination of Treatment Para
- Page 107 and 108: Table 2.5-2: Test Methods Parameter
- Page 109 and 110: Sampling Containerized Waste The te
- Page 111 and 112: Process Waste Solution A discrete p
- Page 113 and 114: ii. The sampling person removes a s
- Page 115 and 116: 2.9 Screening for Ignitable, Reacti
- Page 117 and 118: 3.0 SECURITY PLAN - 40 CFR 270.14(b
- Page 119 and 120: 4.0 INSPECTION PLAN - 40 CFR 270.14
- Page 121 and 122: TSF, associated hazards, places whe
- Page 123 and 124: Outside of working hours, a notific
- Page 125 and 126: Damaged containers will be placed i
- Page 127 and 128: 7.0 PREVENTION AND SAFETY PROCEDURE
- Page 129 and 130: 8.0 PREVENTION OF ACCIDENTAL IGNITI
- Page 131 and 132: 10.0 TRAFFIC - 40 CFR 270.14(b)(10)
- Page 133 and 134: Delivery frequency of reagents will
- Page 135 and 136: 10.3 Traffic Control Signs Traffic
- Page 137 and 138: 11.4 Surrounding Land Use - 40 CFR
- Page 139 and 140: 12.0 PERSONNEL TRAINING PLAN - 40 C
- Page 141 and 142: that are not land based. Closure of
- Page 143 and 144: 13.4.6 Types of Off-site Waste Mana
- Page 145 and 146: 14.0 CLOSED HAZARDOUS WASTE DISPOSA
- Page 147 and 148: storage area (e.g., storage racks),
- Page 149 and 150: 16.0 POST-CLOSURE ESTIMATES - 40 CF
Fire Detection and Control Systems<br />
Where a fire alarm system is listed in Table 1.5-3, the system will typically include smoke<br />
detectors, heat detectors, and/or manual fire pull stations. The fire protection system will also<br />
include the following elements:<br />
Audible and visual alarms.<br />
Automated controls.<br />
o All fire alarm control panels will be supplied by two independent connections<br />
from the power supply.<br />
o Control system will automatically notify appropriate emergency response.<br />
(See Appendix 6-A).<br />
Fire water level and flow detection. Instrumentation will monitor the level of water in<br />
the fire water tank as well as the flow of water.<br />
Proposed TSF Building<br />
Fire extinguishers will be installed throughout the proposed TSF (including the office,<br />
electrical room, and plant spaces).<br />
Sprinklers will be installed to service all areas of the building except the electrical<br />
room. The system will be supplied by a fire water pump and reservoir external to the<br />
proposed TSF.<br />
The Hygiene Dust Collector will be equipped with a sprinkler system and explosion<br />
panels.<br />
Utility Building<br />
Adequate freeze protection will be provided in the fire water supply tank, pumps, and piping. In<br />
addition, the following elements of fire protection are included in the design:<br />
Fire extinguishers will be installed throughout the Utility Building.<br />
Independent detection/suppression systems will be provided with the diesel generator<br />
units.<br />
A one hour fire suppression wall (Fire Wall) is designed to separate the fire water<br />
pump room as per NFPA 20 4.12.1.1.<br />
PMR <strong>RCRA</strong> <strong>Permit</strong> <strong>Application</strong>, <strong>Dry</strong> <strong>Hills</strong> Facility Page 48<br />
JBR Environmental Consultants, Inc. | HATCH March 2013