LON module<br />

for MULTICAL® 601, 602 & 801<br />

D A T A S H E E T<br />

Free topology, FT-X3<br />

For mounting in MULTICAL® 601/602/801<br />

2 pulse inputs<br />

Simple installation with visual module indication (WINK)<br />

Standard twisted pair transceiver, 78 kbit/sec.<br />

Powered by meter supply<br />

Flash program memory (exchangeable software)<br />

Application<br />

The LON module is used for transfer of<br />

data from MULTICAL® 601/602/801<br />

either for data reading or for adjustment<br />

purposes via the LON bus, which<br />

is ideal for i.e. climate control and<br />

building automation. <strong>Data</strong> is communicated<br />

at a high speed which makes<br />

it possible to connect many applications<br />

to the same LON network.<br />

Cabling between the LON module and<br />

the other LON-nodes is made with<br />

a standard twisted pair cable. The<br />

length can be up to 2700 m using bus<br />

topology or 500 m using free topology.<br />

The LON module is built up as a separate<br />

network node with neuron chip,<br />

memory, transceiver and input/output<br />

circuit.<br />

The module requires external supply<br />

(24 VAC /230 VAC) of MULTICAL®<br />

601/602, battery supply is not possible.<br />

The LON module collects new data<br />

from MULTICAL® in a cycle which<br />

secures that all data are updated<br />

every 30 seconds. Network variables<br />

which have been changed compared<br />

with latest reading will be updated on<br />

the bus. All network variables can be<br />

“polled” from other LON nodes in the<br />

network.<br />

If you mark heartbeat data (”HBdata”),<br />

data will be sent every 30<br />

seconds.<br />

Industrivej 28, Stilling · 8660 Skanderborg · Denmark · Tel: +45 89 93 10 00 · Fax: +45 89 93 10 01 · info@kamstrup.com · www.kamstrup.com


LON module for MULTICAL® 601, 602 & 801<br />

DATA SHEET<br />

Network variables<br />

5098861<br />

RevA1<br />

NodeObject<br />

HeatMeter<br />

Flow<br />

Sensor<br />

Flow<br />

Sensor<br />

Temperature Sensors<br />

Pulse<br />

Counter<br />

Pulse<br />

Coun-<br />

ter B<br />

NV<br />

Name<br />

The LON module treats the following MULTICAL® 601/602/801 data as 36 SNVTs (standard network variables):<br />

For further information on SNVT formats see “The SNVT Master List” issued by the Echelon Corporation.<br />

During installation the LON module is self-documenting.<br />

NV<br />

Index<br />

SNVT<br />

Type<br />

Unit<br />

MULTICAL® 601/801<br />

Register<br />

nviRequest 0 SNVT_obj_request Structure Node Request<br />

Description HB<br />

nvoStatus 1 SNVT_obj_status Structure Node Status <br />

nvoInfoCode 2 SNVT_state Structure (*1) Info Info code from MULTICAL® 601/801 <br />

nvoHourCount 3 SNVT_count_f Hour Hour Hour counter from MULTICAL® 601/801<br />

nvoDateTime 4 SNVT_time_stamp<br />

YY:MM:DD<br />

hh:mm:ss<br />

Date & Time Date and Time from MULTICAL® 601/801<br />

nvoE1_HeatV1 5 SNVT_elec_whr_f Wh E1 Heat Energy (V1) <br />

nvoE1_HeatV1_Raw 6 SNVT_reg_val Raw, Unit, Decimal E1 Scaled heat energy (V1) <br />

nvoE2_Control 7 SNVT_elec_whr_f Wh E2 Control energy<br />

nvoE3_Cool 8 SNVT_elec_whr_f Wh E3 Cooling energy <br />

nvoE4_Forward 9 SNVT_elec_whr_f Wh E4 Forward energy<br />

nvoE5_Return 10 SNVT_elec_whr_f Wh E5 Return energy<br />

nvoE6_TapWater 11 SNVT_elec_whr_f Wh E6 Tap water energy<br />

nvoE7_HeatV2 12 SNVT_elec_whr_f Wh E7 Heat energy (V2)<br />

nvoPowerV1 13 SNVT_power_f W Power1 Power (V1) <br />

nvoMeterNo 14 SNVT_str_asc ASCII string Meter No. Meter number <br />

nvoConfigNo 15 SVNT_str_asc ASCII string Config No. Meter configuration DDDEFFGGMN<br />

nvoV1_Volume 16 SNVT _vol_f l V1 V1 Volume <br />

nvoV1_Mass 17 SNVT _mass_f g M1 V1 Mass <br />

nvoV1_Flow 18 SNVT _flow_f l/s Flow1 V1 Flow <br />

nvoV2_Volume 19 SNVT _vol_f l V2 V2 Volume<br />

nvoV2_Mass 20 SNVT _mass_f g M2 V2 Mass<br />

nvoV2_Flow 21 SNVT _flow_f l/s Flow2 V2 Flow<br />

nvoTemperature1 22 SNVT_temp_p °C T1 Temperature T1 <br />

nvoTemperature2 23 SNVT_temp_p °C T2 Temperature T2 <br />

nvoTemperature3 24 SNVT_temp_p °C T3 Temperature T3<br />

nvoTemperature4 25 SNVT_temp_p °C T4 Temperature T4<br />

nvoTemperatuDiff 26 SNVT_temp_p °C T1-T2 Temperature difference (T1-T2) <br />

nvoPulseVA_Vol 27 SNVT_vol_f l Pulse input A Volume Pulse input VA Volume<br />

nvoPulseVA_E 28 SNVT_elec_whr_f Wh Pulse input A Energy Pulse input VA Energy<br />

nvoPulseVB_Vol 29 SNVT_vol_f l Pulse input B Volume Pulse input VB Volume<br />

nvoPulseVB_E 30 SNVT_elec_whr_f Wh Pulse input B Energy Pulse input VB Energy<br />

nvoV1_Volume_Raw 31 SNVT_reg_val Raw. Unit Decimal V1<br />

V1 Volume<br />

As shown in MULTICAL® display.<br />

nvoV2_Volume_Raw 32 SNVT_reg_val Raw. Unit Decimal V2<br />

V2 Volume<br />

As shown in MULTICAL® display.<br />

nvoE3_Cool_Raw 33 SNVT_reg_val Raw. Unit Decimal E3<br />

Cooling Energy<br />

As shown in MULTICAL® display.<br />

nvoMeterType 34 SNVT_str_asc ASCII string<br />

nviDateTime 35 SNVT_time_stamp YY:MM:DD Date & Time New date and time for MULTICAL®<br />

nviHeartbeat 36 SNVT_count Off or 30 sec 30 sec heartbeat (for nvos marked ) <br />

2 58101043_A1_GB_03.2012


LON module for MULTICAL® 601, 602 & 801<br />

DATA SHEET<br />

Technical data<br />

58101043_A1_GB_03.2012<br />

*1) 16 bit structure, which represents the info codes of MULTICAL® 601/602/801<br />

Bit 0: MULTICAL® reset<br />

Bit 1: -n/a-<br />

Bit 2: Temperature sensor T2 outside measuring range<br />

Bit 3: Temperature sensor T1 outside measuring range<br />

Bit 4: Flow sensor V1, communication error<br />

Bit 5: Temperature sensor T3 outside measuring range<br />

Bit 6: Leak in cold water system<br />

Bit 7: Flow sensor V2 pulse figure error<br />

Bit 8: Leak in heating system<br />

Bit 9: Burst in heating system<br />

Bit 10 Flow sensor V2 communication error<br />

Bit 11 Flow sensor V1 pulse figure error<br />

Bit 12 Flow sensor V1 air problem<br />

Bit 13 Flow sensor V2 air problem<br />

Bit 14 Flow sensor V1 wrong flow direction<br />

Bit 15: Flow sensor V2 wrong flow direction<br />

Electrical data<br />

Some info codes do not apply to all meters.<br />

See Technical Description of the MULTICAL® 601/602/801 in question for details.<br />

Supply Powered by MULTICAL® supply.<br />

Current consumption


LON module for MULTICAL® 601, 602 & 801<br />

DATA SHEET<br />

Technical data<br />

Software<br />

Ordering details<br />

Mechanical data<br />

Dimensions, WxHxD 90x70x20 mm<br />

Ambient temperature 0…55°C<br />

Mounting For mounting in MULTICAL® 601/602/801<br />

Marking/Approvals<br />

PTB and TS approved for mounting in MULTICAL® 601/602/801<br />

CE-marking applies when the LON module is mounted in MULTICAL® 601/602/801<br />

New software for update or extension of the module can be downloaded to the module via the LON<br />

network.<br />

Description Type no.<br />

LON module for MULTICAL® 601 670024000-000<br />

LON module for MULTICAL® 602 6020024000-000<br />

LON module for MULTICAL® 801, module 1 670024000-000<br />

LON module for MULTICAL® 801, module 2 670Y00000-000<br />

XIF files and standard software are available on www.kamstrup.dk<br />

4 58101043_A1_GB_03.2012