LON module<br />
for MULTICAL® 601, 602 & 801<br />
D A T A S H E E T<br />
Free topology, FT-X3<br />
For mounting in MULTICAL® 601/602/801<br />
2 pulse inputs<br />
Simple installation with visual module indication (WINK)<br />
Standard twisted pair transceiver, 78 kbit/sec.<br />
Powered by meter supply<br />
Flash program memory (exchangeable software)<br />
Application<br />
The LON module is used for transfer of<br />
data from MULTICAL® 601/602/801<br />
either for data reading or for adjustment<br />
purposes via the LON bus, which<br />
is ideal for i.e. climate control and<br />
building automation. <strong>Data</strong> is communicated<br />
at a high speed which makes<br />
it possible to connect many applications<br />
to the same LON network.<br />
Cabling between the LON module and<br />
the other LON-nodes is made with<br />
a standard twisted pair cable. The<br />
length can be up to 2700 m using bus<br />
topology or 500 m using free topology.<br />
The LON module is built up as a separate<br />
network node with neuron chip,<br />
memory, transceiver and input/output<br />
circuit.<br />
The module requires external supply<br />
(24 VAC /230 VAC) of MULTICAL®<br />
601/602, battery supply is not possible.<br />
The LON module collects new data<br />
from MULTICAL® in a cycle which<br />
secures that all data are updated<br />
every 30 seconds. Network variables<br />
which have been changed compared<br />
with latest reading will be updated on<br />
the bus. All network variables can be<br />
“polled” from other LON nodes in the<br />
network.<br />
If you mark heartbeat data (”HBdata”),<br />
data will be sent every 30<br />
seconds.<br />
Industrivej 28, Stilling · 8660 Skanderborg · Denmark · Tel: +45 89 93 10 00 · Fax: +45 89 93 10 01 · info@kamstrup.com · www.kamstrup.com
LON module for MULTICAL® 601, 602 & 801<br />
DATA SHEET<br />
Network variables<br />
5098861<br />
RevA1<br />
NodeObject<br />
HeatMeter<br />
Flow<br />
Sensor<br />
Flow<br />
Sensor<br />
Temperature Sensors<br />
Pulse<br />
Counter<br />
Pulse<br />
Coun-<br />
ter B<br />
NV<br />
Name<br />
The LON module treats the following MULTICAL® 601/602/801 data as 36 SNVTs (standard network variables):<br />
For further information on SNVT formats see “The SNVT Master List” issued by the Echelon Corporation.<br />
During installation the LON module is self-documenting.<br />
NV<br />
Index<br />
SNVT<br />
Type<br />
Unit<br />
MULTICAL® 601/801<br />
Register<br />
nviRequest 0 SNVT_obj_request Structure Node Request<br />
Description HB<br />
nvoStatus 1 SNVT_obj_status Structure Node Status <br />
nvoInfoCode 2 SNVT_state Structure (*1) Info Info code from MULTICAL® 601/801 <br />
nvoHourCount 3 SNVT_count_f Hour Hour Hour counter from MULTICAL® 601/801<br />
nvoDateTime 4 SNVT_time_stamp<br />
YY:MM:DD<br />
hh:mm:ss<br />
Date & Time Date and Time from MULTICAL® 601/801<br />
nvoE1_HeatV1 5 SNVT_elec_whr_f Wh E1 Heat Energy (V1) <br />
nvoE1_HeatV1_Raw 6 SNVT_reg_val Raw, Unit, Decimal E1 Scaled heat energy (V1) <br />
nvoE2_Control 7 SNVT_elec_whr_f Wh E2 Control energy<br />
nvoE3_Cool 8 SNVT_elec_whr_f Wh E3 Cooling energy <br />
nvoE4_Forward 9 SNVT_elec_whr_f Wh E4 Forward energy<br />
nvoE5_Return 10 SNVT_elec_whr_f Wh E5 Return energy<br />
nvoE6_TapWater 11 SNVT_elec_whr_f Wh E6 Tap water energy<br />
nvoE7_HeatV2 12 SNVT_elec_whr_f Wh E7 Heat energy (V2)<br />
nvoPowerV1 13 SNVT_power_f W Power1 Power (V1) <br />
nvoMeterNo 14 SNVT_str_asc ASCII string Meter No. Meter number <br />
nvoConfigNo 15 SVNT_str_asc ASCII string Config No. Meter configuration DDDEFFGGMN<br />
nvoV1_Volume 16 SNVT _vol_f l V1 V1 Volume <br />
nvoV1_Mass 17 SNVT _mass_f g M1 V1 Mass <br />
nvoV1_Flow 18 SNVT _flow_f l/s Flow1 V1 Flow <br />
nvoV2_Volume 19 SNVT _vol_f l V2 V2 Volume<br />
nvoV2_Mass 20 SNVT _mass_f g M2 V2 Mass<br />
nvoV2_Flow 21 SNVT _flow_f l/s Flow2 V2 Flow<br />
nvoTemperature1 22 SNVT_temp_p °C T1 Temperature T1 <br />
nvoTemperature2 23 SNVT_temp_p °C T2 Temperature T2 <br />
nvoTemperature3 24 SNVT_temp_p °C T3 Temperature T3<br />
nvoTemperature4 25 SNVT_temp_p °C T4 Temperature T4<br />
nvoTemperatuDiff 26 SNVT_temp_p °C T1-T2 Temperature difference (T1-T2) <br />
nvoPulseVA_Vol 27 SNVT_vol_f l Pulse input A Volume Pulse input VA Volume<br />
nvoPulseVA_E 28 SNVT_elec_whr_f Wh Pulse input A Energy Pulse input VA Energy<br />
nvoPulseVB_Vol 29 SNVT_vol_f l Pulse input B Volume Pulse input VB Volume<br />
nvoPulseVB_E 30 SNVT_elec_whr_f Wh Pulse input B Energy Pulse input VB Energy<br />
nvoV1_Volume_Raw 31 SNVT_reg_val Raw. Unit Decimal V1<br />
V1 Volume<br />
As shown in MULTICAL® display.<br />
nvoV2_Volume_Raw 32 SNVT_reg_val Raw. Unit Decimal V2<br />
V2 Volume<br />
As shown in MULTICAL® display.<br />
nvoE3_Cool_Raw 33 SNVT_reg_val Raw. Unit Decimal E3<br />
Cooling Energy<br />
As shown in MULTICAL® display.<br />
nvoMeterType 34 SNVT_str_asc ASCII string<br />
nviDateTime 35 SNVT_time_stamp YY:MM:DD Date & Time New date and time for MULTICAL®<br />
nviHeartbeat 36 SNVT_count Off or 30 sec 30 sec heartbeat (for nvos marked ) <br />
2 58101043_A1_GB_03.2012
LON module for MULTICAL® 601, 602 & 801<br />
DATA SHEET<br />
Technical data<br />
58101043_A1_GB_03.2012<br />
*1) 16 bit structure, which represents the info codes of MULTICAL® 601/602/801<br />
Bit 0: MULTICAL® reset<br />
Bit 1: -n/a-<br />
Bit 2: Temperature sensor T2 outside measuring range<br />
Bit 3: Temperature sensor T1 outside measuring range<br />
Bit 4: Flow sensor V1, communication error<br />
Bit 5: Temperature sensor T3 outside measuring range<br />
Bit 6: Leak in cold water system<br />
Bit 7: Flow sensor V2 pulse figure error<br />
Bit 8: Leak in heating system<br />
Bit 9: Burst in heating system<br />
Bit 10 Flow sensor V2 communication error<br />
Bit 11 Flow sensor V1 pulse figure error<br />
Bit 12 Flow sensor V1 air problem<br />
Bit 13 Flow sensor V2 air problem<br />
Bit 14 Flow sensor V1 wrong flow direction<br />
Bit 15: Flow sensor V2 wrong flow direction<br />
Electrical data<br />
Some info codes do not apply to all meters.<br />
See Technical Description of the MULTICAL® 601/602/801 in question for details.<br />
Supply Powered by MULTICAL® supply.<br />
Current consumption
LON module for MULTICAL® 601, 602 & 801<br />
DATA SHEET<br />
Technical data<br />
Software<br />
Ordering details<br />
Mechanical data<br />
Dimensions, WxHxD 90x70x20 mm<br />
Ambient temperature 0…55°C<br />
Mounting For mounting in MULTICAL® 601/602/801<br />
Marking/Approvals<br />
PTB and TS approved for mounting in MULTICAL® 601/602/801<br />
CE-marking applies when the LON module is mounted in MULTICAL® 601/602/801<br />
New software for update or extension of the module can be downloaded to the module via the LON<br />
network.<br />
Description Type no.<br />
LON module for MULTICAL® 601 670024000-000<br />
LON module for MULTICAL® 602 6020024000-000<br />
LON module for MULTICAL® 801, module 1 670024000-000<br />
LON module for MULTICAL® 801, module 2 670Y00000-000<br />
XIF files and standard software are available on www.kamstrup.dk<br />