30.06.2013 Views

Untitled

Untitled

Untitled

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

CIP Distribution Piping Systems 191<br />

CIPS valve group. On the inlet side of this valve group, lines slope back to the CIP<br />

system and on the discharge side, lines slope toward the process area destination.<br />

Likewise, for CIPR piping, there is ahigh point from where lines slope either back to<br />

the CIPR pump at the tank being cleaned or forward to CIPR at the central<br />

CIP system.<br />

As with all sanitary piping systems, proper installation methods must be used<br />

to ensure that piping is not only “hung” but also supported, so as to retain the<br />

original intended slope. Permanently installed spray devices should be installed<br />

using aspray supply connecting manifold that allows for easy removal. The CIPS<br />

piping and the spray manifold should be supported so that stress is not present at<br />

clamps, which could cause poor alignment and leaking.<br />

Areas requiring routine access by operators or maintenance personnel must<br />

be preplanned. There is need to access sample points in the CIPS and CIPR<br />

distribution piping. This includes both sample valves used to obtain solution<br />

during various points of the CIP cycle as well as piping access locations to be<br />

used for swabbing during cleaning validation. Also, permanently installed valves<br />

must be accessible for routine maintenance.<br />

CIPS AND CIPR HYDRAULIC CONSIDERATIONS<br />

Before starting to design aCIPS and CIPR piping system, an understanding of<br />

the hydraulic factors is important. Figure 12 illustrates the concepts discussed<br />

below.<br />

CIPS hydraulic factors for tank circuits are as follows:<br />

& CIPS static head loss is due to the difference in height between the CIP<br />

recirculation tank level and the spray device of the process tank being<br />

cleaned (Fig. 12, elevation REF AtoREF B).<br />

& CIPR static head loss is due to the difference in height between the process tank<br />

level and the CIP recirculation tank return point connection at aspray device,<br />

nozzle, etc. (Fig. 12, elevation REF CtoREF D).<br />

& CIPS and return friction head loss is due to the energy necessary to move flow<br />

through the piping system at agiven flow rate. The manufacturers of sanitary<br />

components often publish data tables for friction head loss through valve,<br />

fittings, and sanitary tubing. Note that sanitary “OD tubing” has different<br />

internal diameter than industrial “schedule piping” and, therefore, industrial<br />

friction loss data tables are not correct for sanitary OD tubing design.<br />

& The CIP spray device has arequired operating pressure, both on the CIPS side<br />

in the case of the process tank being cleaned and on the CIPR side if aspray<br />

device is used for recycle of flow back to the CIP system.<br />

Thus, the total CIPS or CIPR head requirement is the sum of static head, friction<br />

head, and spray device operating pressure.<br />

For line circuits, ( i )there is no spray device involved for atarget vessel being<br />

cleaned, ( ii)static head loss is minimal because flow both begins and ends at the CIP<br />

system, and ( iii)aCIPR pump is not required.Inthis case, the hydraulic calculation<br />

is reduced to the sum of friction head loss for CIPS and CIPR piping, possibly plus<br />

the operating pressureofaspray device if one is used for recycle of flow back to the<br />

CIP system.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!