30.06.2013 Views

Untitled

Untitled

Untitled

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

184<br />

Lebowitz<br />

oriented vertically. This is the least preferred orientation since an uncleanable<br />

vertical dead-leg “trap” is created in the distance between flow traveling through<br />

the main header and the diaphragm of the valve.<br />

The horizontally oriented valves located above TP-3 are an acceptable<br />

arrangement as long as the distance between the center of the main flow path<br />

and diaphragm valve weir is less than two pipe diameters.<br />

The preferred orientation is the zero-static type diaphragm valves located<br />

above TP-5. In this case, the zero-static valves ensure that there isessentially no<br />

dead leg between the main flow path and diaphragm valve weir.<br />

CIPS and CIPR Loops<br />

The isometric drawing of Figure 7illustrates asingle CIP system that services<br />

various process areas in a biopharmaceutical facility. A composite of various<br />

methods of installing CIPS and CIPR is shown in this example. All concepts<br />

assure complete freedom offlow dead legs and provide essentially uniform<br />

operating volumes and times for all tank CIP programs. One of the two primary<br />

CIPS control valves located just beyond the CIP system branches toward the CIPS<br />

header supplying MT-1 through MT-3, the remainder of the area being in<br />

accordance with Figure 6asdescribed above. CIPR pump RP-1 discharges to a<br />

CIPR distribution valve before the final line to the CIP skid.<br />

Loop-type piping is shown in Figure 7for the CIPS and CIPR connections to<br />

tanks T-4 toT-9.<br />

Permanent product pump PP/RP, also used as aCIPR pump (which might<br />

include variable frequency drive (VFD) variable speed capacity control), is located<br />

at the discharge of T-5. Aportable CIPR pump (RP-2) is used for T-4and T-6(shown<br />

connected) and apermanent CIPR pump (RP-3) on low-level transfer panel TP-10 is<br />

used for T-7 toT-9.<br />

An alternative “loop-type” CIPS/R concept is illustrated as the means of<br />

providing CIPS/R capability to tanks T-4 to T-9 inclusive in several different<br />

manners. The objective of this revised approach is twofold and includes totally<br />

eliminating the possibility of any “dead ends” in that portion of the system in use<br />

and providing auniform supply and return path for each of the tanks in the several<br />

groups at various locations within the facility.<br />

Four different methods of providing pumped return are illustrated in<br />

Figure 7. These include the following.<br />

1. Apermanently installed return pump RP-1 supplied by the header at vessels<br />

MT-1 through MT-3, as described above, engineered and specified to serve the<br />

CIP solution return need only.<br />

2. Acentrifugal pump PP/RP installed in the discharge line of vessel T-5 and<br />

equipped with aVFD for capacity control would be used for product transfers<br />

and CIPR.<br />

3. Aportable CIPR pump RP-2 would be used at tanks T-4 and T-6. This pump<br />

would connect via ahose directly to the tank outlet valve of T-4ortothe port on<br />

TP-9 for T-6, and via another hose to aCIPR port on TP-7 or TP-9. The suctionside<br />

hoses must be short and installed to maintain continuous pitch upwards<br />

from the return pump inlet to the tank outlet valve for efficient and reliable<br />

performance of the CIP system.<br />

4. Apermanently installed return pump RP-3 is shown as the means of returning<br />

solution from vessels T-7toT-9, which connect to ports on TP-10. For CIPR, the

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!