CIP System Instrumentation and Controls 127<br />

water and the overall design of the vessel can interfere with proper performance of<br />

these devices.<br />

Supply Pressure Monitoring and Control<br />

Unlike their level sensing counterparts, the use of modern sanitary diaphragm<br />

type pressure transmitters to measure CIP supply pressure will work very well as<br />

the effects due to temperature variation are almost negligible. Also the role of the<br />

pressure transmitter is much less critical in nature and is generally used as more of a<br />

monitoring device than regulating device in CIP applications.<br />

Many applications interlock the chemical feed sequences and the heating<br />

controls so that these systems cannot be operated if aminimum supply pressure is<br />

not maintained. This is implemented as asafety measure toprevent steam and<br />

chemicals to be applied to the system when the supply pump is not discharging<br />

water or CIP solution. This interlock function could also be readily applied utilizing<br />

a minimum flow setpoint instead and is frequently the means utilized in<br />

pharmaceutical applications.<br />

Return Flow Check<br />

For years the food and dairy industry has incorporated instrumentation in the CIP<br />

return line to check and verify that the first pre-rinse ofthe CIP program has<br />

successfully returned back to the CIP unit. Failure of the return flow check would<br />

result in an aborted CIP program along with an appropriate alarm message to the<br />

operator.This functionality was primarily provided to ensurethat all manual swing<br />

connections on the CIP supply side and CIP return side were configured properly.<br />

Even with the advent of fully automated hard piped mixproof valve systems, it is<br />

still considered good practice to include this functionality in all applications,<br />

including pharmaceutical.<br />

The Conductivity Sensing Element<br />

The instrument of choice for many years has been an inexpensive sanitary stainless<br />

steel probe mounted in an insulating material and clamped in place within a<br />

shallow tee fitting. The probe is, in turn, wired to arelay designed to trigger based<br />

upon the difference in conductivity between air and water. These conductivity<br />

probes were originally designed to be used for discrete liquid level controls, but<br />

have also served reliably in this application many times over.One must be careful to<br />

specify an appropriate relay with aconductivity range which will work with the<br />

water to be used in the application, however. Water such as water-for-injection will<br />

require avery sensitive relay that can detect very low conductivity levels.<br />

Recently, some pharmaceutical users have rejected the use of these devices as<br />

the manufacturers of them have been slow to provide proper material certifications<br />

and/or performance specifications for their products. Hopefully, this situation will<br />

improve over time such that product acceptance will not be aproblem.<br />

The “Tuning Fork”<br />

Amore recent alternative to the conductivity-based device is another instrument<br />

that was designed originally with level sensing in mind. The “tuning fork” level<br />

switch utilizes apair of paddles that vibrate at aknown resonant frequency. When<br />

the forks are immersed in aliquid, the frequency changes and the associated<br />

electronics detect the change. These tuning fork devices have also been used