Date: 10-15-12 INITIATED BY: Cynthia Collazo Deputy City Manager COUNCIL COMMUNICATION SUBJECT: PUBLIC HEARING AND INTRODUCTORY ODINANCE AMENDING CHAPTER 12 FIRE PREVENTION AND PROTECTION OF THE CODE OF ORDINANCES BY AMENDING SECTION 12-2 TO ADOPT THE 2012 EDITION OF INTERNATIONAL FIRE CODE WITH THE FOLLOWING AMENDMENTS: 1) SECTION 507.5.1 WHERE REQUIRED. FIRE HYDRANTS SHALL BE PROVIDED ALONG PUBLIC AND PRIVATE STREETS AT EVERY 300 FEET FOR COMMERCIAL DEVELOPMENT AND EVERY 500 FEET FOR RESIDENTIAL DEVELOPMENT. AND WHERE A PORTION OF THE FACILITY OR BUILDING HEREAFTER CONSTRUCTED OR MOVED INTO OR WITHIN THE JURISDICTION IS MORE THAN 400 FEET ( 122 M) FROM A HYDRANT ON A FIRE APPARATUS ACCESS ROAD, AS MEASURED BY AN APPROVED ROUTE AROUND THE EXTERIOR OF THE FACILITY OR BUILDING, ON- SITE FIRE HYDRANTS AND MAINS SHALL BE PROVIDED WHERE REQUIRED BY THE FIRE CODE OFFICIAL. EXCEPTIONS: 1. FIRE GROUP R-3 AND GROUP U OCCUPANCIES, THE DISTANCE REQUIREMENT SHALL BE 600 FEET (183M). 2. FOR BUILDINGS EQUIPPED THROUGHOUT WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2, THE DISTANCE REQUIREMENT SHALL BE 600 FEET (1 83M). 2) SECTION 507.5.7 MARKING OF FlRE HYDRANT LOCATIONS. RAISED BLUE PAVEMENT MARKERS SHALL BE PROVIDED ON PUBLIC AND PRIVATE STREETS TO INDICATE THE LOCATIONS OF FIRE HYDRANTS. THESE MARKERS SHALL BE PLACED JUST OFF CENTER TO THE SIDE THE FIRE HYDRANT IS LOCATED. 3) SECTION 903.2 WHERE REQUIRED. APPROVED AUTOMATIC SPRINKLER SYSTEMS IN NEW BUILDINGS AND STRUCTURES SHALL BE PROVIDED IN ANY BUILDING REGARDLESS OF OCCUPANCY TYPE IN WHICH THE TOTAL FIRE AREAS WITHIN THE EXTERIOR WALLS EXCEED 12.000 SQUARE FEET, AND SHALL ALSO BE PROVIDED IN THE LOCATIONS DESCRIBED IN SECTIONS 903.2.1 THROUGH 903.2.12. EXCEPTIONS: SPACES OR AREAS IN TELECOMMUNICATIONS BUILDINGS USED EXCLUSIVELY FOR TELECOMMUNICATIONS EQUIPMENT, ASSOCIATED ELECTRICAL POWER DISTRIBUTION EQUIPMENT, BATTERIES AND STANDBY ENGINES, PROVIDED THOSE SPACES OR AREAS ARE EQUIPPED THROUGHOUT WITH AN AUTOMATIC SMOKE DETECTION SYSTEM IN ACCORDANCE WITH SECTION 907.2 AND ARE SEPARATED FROM THE REMAINDER OF THE BUILDING BY NOT LESS THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OF THE INTERNATIONAL BUILDING CODE OR NOT LESS THAN ZHOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH SECTION 71 1 OF THE INTERNATIONAL BUILDING CODE, OR BOTH. 4) SECTION 903.2.8 GROW R AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R FIRE AREA. EXCEPTION: AN AUTOMATIC SPRINKLER SYSTEM IS NOT REOUIRED IN GROUP R-2 APARTMENT HOUSES WITH A MAXIMUM DWELLING OF FOUR UNITS IN WHICH THE UNITS ARE SUBDIVIDED INTO GROUPS OF TWO BY A VERTICAL FIRE WALL WITH A FIRE RATING OF NO LESS THAN TWO HOURS. 5) SECTION 903.3.1.2.2 BREEZEWAYS. SPRINKLER PROTECTION SHALL BE PROVIDED IN BREEZEWAYS OF GROUP R OCCUPANCIES WHERE BUILDINGS ARE OF TYPE FIVE CONSTRUCTION. PROVIDING A SEVERABILITY, SAVINGS, REPEALING, AND PENALTY CLAUSE; ESTABLISHING AN EFFECTIVE DATE; AND PROVIDING FOR PUBLICATION. STAFF SOURCE: Steve Landin, Fire Chief PREVIOUS COUNCIL ACTION: On January 4,2010, the City of Laredo adopted the 2009 Fire Code. *
BACKGROUND: The Fire Chief with concurrence from the Building Development Services Department Director recommends amendments to the Fire Code as stated above which are applicable to the City, a home rule municipality. FINANCIAL IMPACT: None COMMITTEE RECOMMENDATION: STAFF RECOMMENDATION: Staff recommends that City Council approve this ordinance.
- Page 1 and 2: CITY OF LAREDO CITY COUNCIL MEETING
- Page 3 and 4: 25-6 International Fuel Gas Code, t
- Page 5 and 6: 9. Public hearing and introductory
- Page 7 and 8: All being situated in the Eastern D
- Page 9 and 10: 0922-33-109 (1.0 miles south of SH
- Page 11 and 12: assurance for the Laredo Internatio
- Page 13 and 14: XIII. STAFF REPORTS 4. Presentation
- Page 15 and 16: COUNCIL COMMUNICATION DATE: I SUBJE
- Page 17 and 18: ORDINANCE AUTHORIZING THE CITY MANA
- Page 19 and 20: DATE: COUNCIL COMMUNICATION SUBJECT
- Page 21 and 22: PASSED BY THE CITY COUNCIL AND APPR
- Page 23 and 24: AN ORDINANCE ACCEPTING A GRANT FROM
- Page 25 and 26: COUNCIL COMMUNICATION DATE: SUBJECT
- Page 27 and 28: PASSED BY THE CITY COUNCIL AND APPR
- Page 29 and 30: ORDINANCE NO. AMENDING CHAPTER 11 E
- Page 31 and 32: Date: 10-15-2012 INITIATED BY: COUN
- Page 33: Section 5. That this Ordinance and
- Page 37 and 38: WHEREAS, on January 4, 2010, by Ord
- Page 39 and 40: DATE 10-15-12 INITIATED BY: Horacio
- Page 41 and 42: Part 1: Section 7-1. Code-Adopted.
- Page 43 and 44: Date: 10/15/12 Initiated by: Cornel
- Page 45 and 46: CITY OF LAREDO ORDINANCE NO. 2012-0
- Page 47: UNPLATTED
- Page 52 and 53: 1 t Warranty: Because the condition
- Page 54 and 55: INGREDIENT: NONE SECTION 2 - HAZARD
- Page 56 and 57: INHALATION: REMOVE TO FRESH AIR HOW
- Page 58 and 59: , K+M:[C;N.. PR3i:XJI."I' and LTMI:
- Page 60 and 61: d%ath. I ly c1vvnj.c exposure of an
- Page 62 and 63: IR'T MMHF:R: 'W HIM, INT. R4I-E: 00
- Page 64 and 65: ndar has adop.t~J the ACIXIH R.Ui r
- Page 66 and 67: R'T MMER: 703 WPM (EA IK, NQI tK!14
- Page 68 and 69: WPAK I.&> IK- PAGE: 011. MEPI~L ?E&
- Page 70 and 71: 1 DR1' MMFn:H : 7!)3 w)~-%u! IN::.
- Page 72 and 73: PRODUCT NAME: CHEMICAL NAME: I - CH
- Page 74 and 75: I PAGE 3 PRODUCT NAME: '[RIETHYLENE
- Page 76 and 77: HP~~ARDous POLYMERI~ATI~N: wlil Not
- Page 78 and 79: PRODUCT NAME: ITRIFTHYLENE GLYCOL i
- Page 80 and 81: Material Safety Data Sheet ~ I 1 I
- Page 82 and 83: Material ~afetd Data Sheet I Shell
Date:<br />
10-<strong>15</strong>-12<br />
INITIATED BY:<br />
Cynthia Collazo<br />
Deputy <strong>City</strong> Manager<br />
COUNCIL COMMUNICATION<br />
SUBJECT: PUBLIC HEARING AND INTRODUCTORY ODINANCE<br />
AMENDING CHAPTER 12 FIRE PREVENTION AND PROTECTION OF THE CODE OF<br />
ORDINANCES BY AMENDING SECTION 12-2 TO ADOPT THE <strong>2012</strong> EDITION OF<br />
INTERNATIONAL FIRE CODE WITH THE FOLLOWING AMENDMENTS:<br />
1) SECTION 507.5.1 WHERE REQUIRED. FIRE HYDRANTS SHALL BE PROVIDED<br />
ALONG PUBLIC AND PRIVATE STREETS AT EVERY 300 FEET FOR COMMERCIAL<br />
DEVELOPMENT AND EVERY 500 FEET FOR RESIDENTIAL DEVELOPMENT. AND<br />
WHERE A PORTION OF THE FACILITY OR BUILDING HEREAFTER CONSTRUCTED OR<br />
MOVED INTO OR WITHIN THE JURISDICTION IS MORE THAN 400 FEET ( 122 M) FROM<br />
A HYDRANT ON A FIRE APPARATUS ACCESS ROAD, AS MEASURED BY AN<br />
APPROVED ROUTE AROUND THE EXTERIOR OF THE FACILITY OR BUILDING, ON-<br />
SITE FIRE HYDRANTS AND MAINS SHALL BE PROVIDED WHERE REQUIRED BY THE<br />
FIRE CODE OFFICIAL.<br />
EXCEPTIONS:<br />
1. FIRE GROUP R-3 AND GROUP U OCCUPANCIES, THE DISTANCE REQUIREMENT<br />
SHALL BE 600 FEET (183M).<br />
2. FOR BUILDINGS EQUIPPED THROUGHOUT WITH AN APPROVED AUTOMATIC<br />
SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR<br />
903.3.1.2, THE DISTANCE REQUIREMENT SHALL BE 600 FEET (1 83M).<br />
2) SECTION 507.5.7 MARKING OF FlRE HYDRANT LOCATIONS. RAISED BLUE<br />
PAVEMENT MARKERS SHALL BE PROVIDED ON PUBLIC AND PRIVATE STREETS TO<br />
INDICATE THE LOCATIONS OF FIRE HYDRANTS. THESE MARKERS SHALL BE<br />
PLACED JUST OFF CENTER TO THE SIDE THE FIRE HYDRANT IS LOCATED.<br />
3) SECTION 903.2 WHERE REQUIRED. APPROVED AUTOMATIC SPRINKLER<br />
SYSTEMS IN NEW BUILDINGS AND STRUCTURES SHALL BE PROVIDED IN ANY<br />
BUILDING REGARDLESS OF OCCUPANCY TYPE IN WHICH THE TOTAL FIRE AREAS<br />
WITHIN THE EXTERIOR WALLS EXCEED 12.000 SQUARE FEET, AND SHALL ALSO BE<br />
PROVIDED IN THE LOCATIONS DESCRIBED IN SECTIONS 903.2.1 THROUGH 903.2.12.<br />
EXCEPTIONS: SPACES OR AREAS IN TELECOMMUNICATIONS BUILDINGS USED<br />
EXCLUSIVELY FOR TELECOMMUNICATIONS EQUIPMENT, ASSOCIATED<br />
ELECTRICAL POWER DISTRIBUTION EQUIPMENT, BATTERIES AND STANDBY<br />
ENGINES, PROVIDED THOSE SPACES OR AREAS ARE EQUIPPED THROUGHOUT WITH<br />
AN AUTOMATIC SMOKE DETECTION SYSTEM IN ACCORDANCE WITH SECTION 907.2<br />
AND ARE SEPARATED FROM THE REMAINDER OF THE BUILDING BY NOT LESS<br />
THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707<br />
OF THE INTERNATIONAL BUILDING CODE OR NOT LESS THAN ZHOUR<br />
HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH SECTION 71 1 OF<br />
THE INTERNATIONAL BUILDING CODE, OR BOTH.<br />
4) SECTION 903.2.8 GROW R AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN<br />
ACCORDANCE WITH SECTION 903.3 SHALL BE PROVIDED THROUGHOUT ALL<br />
BUILDINGS WITH A GROUP R FIRE AREA.<br />
EXCEPTION: AN AUTOMATIC SPRINKLER SYSTEM IS NOT REOUIRED IN GROUP R-2<br />
APARTMENT HOUSES WITH A MAXIMUM DWELLING OF FOUR UNITS IN WHICH THE<br />
UNITS ARE SUBDIVIDED INTO GROUPS OF TWO BY A VERTICAL FIRE WALL WITH A<br />
FIRE RATING OF NO LESS THAN TWO HOURS.<br />
5) SECTION 903.3.1.2.2 BREEZEWAYS. SPRINKLER PROTECTION SHALL BE<br />
PROVIDED IN BREEZEWAYS OF GROUP R OCCUPANCIES WHERE BUILDINGS ARE OF<br />
TYPE FIVE CONSTRUCTION.<br />
PROVIDING A SEVERABILITY, SAVINGS, REPEALING, AND PENALTY CLAUSE;<br />
ESTABLISHING AN EFFECTIVE DATE; AND PROVIDING FOR PUBLICATION.<br />
STAFF SOURCE:<br />
Steve Landin, Fire Chief<br />
PREVIOUS COUNCIL ACTION:<br />
On January 4,2010, the <strong>City</strong> <strong>of</strong> <strong>Laredo</strong> adopted the 2009 Fire Code.<br />
*