Figure 4.55. Interior beam-to-column joint measurement<br />

equipment<br />

4.10.2 Results <strong>of</strong> <strong>the</strong> PsD test n° 1<br />

The <strong>behaviour</strong> <strong>of</strong> <strong>the</strong> structure was essentially elastic <strong>and</strong> no damage could be<br />

observed at <strong>the</strong> beam-to-column joints <strong>and</strong> at <strong>the</strong> base joints. Only at <strong>the</strong> bottom<br />

storey some little cracks were present on <strong>the</strong> slab in <strong>the</strong> joint areas, all parallel to<br />

<strong>the</strong> transverse beams <strong>and</strong> starting from <strong>the</strong> edges <strong>of</strong> <strong>the</strong> steel sections <strong>of</strong> <strong>the</strong><br />

columns. Due to <strong>the</strong> presence <strong>of</strong> <strong>the</strong> concrete blocks at <strong>the</strong> second level, cracking<br />

developed in <strong>the</strong> transverse direction, mainly on <strong>the</strong> column line. At <strong>the</strong> first step <strong>of</strong><br />

<strong>the</strong> Spatial Model procedure <strong>the</strong> frequencies <strong>of</strong> <strong>the</strong> first <strong>and</strong> second mode have<br />

values equal to 2.31 Hz <strong>and</strong> to 7.81 Hz, respectively. The mean value <strong>of</strong> <strong>the</strong> modal<br />

damping is very low, equal to 1.03% for <strong>the</strong> first mode <strong>and</strong> to 0.69% for <strong>the</strong> second<br />

one. The maximum interstorey drifts reached at <strong>the</strong> first <strong>and</strong> second level are –9.7<br />

mm <strong>and</strong> –12.3 mm, respectively. These correspond to a value <strong>of</strong> about 0.35% <strong>of</strong><br />

<strong>the</strong> interstorey height.<br />

4.10.3 Results <strong>of</strong> <strong>the</strong> PsD test n° 2<br />

The objective <strong>of</strong> <strong>the</strong> second test was to induce into <strong>the</strong> structure a first yielding with<br />

no excessive damage. From a first visual inspection it could be observed that:<br />

• no damage occurred at <strong>the</strong> column base, no crashing or spalling <strong>of</strong> <strong>the</strong><br />

concrete <strong>and</strong> no local buckling in <strong>the</strong> steel flanges;<br />