Installation Instructions for TTDM Alarm <strong>and</strong> Locating <strong>Module</strong><br />

Connecting the Sensing Cable Start-Up <strong>and</strong> System Testing<br />

Prepare sensing cable.<br />

Ensure that the sensing cable has been installed <strong>and</strong> tested in<br />

accordance with the instructions provided with the cable.<br />

Make connections.<br />

• Confirm that power to the unit has been shut off.<br />

• Open the enclosure door.<br />

• Feed the end of the <strong>TraceTek</strong> Modular Leader Cable (or Jumper<br />

Cable) through the adapter/bushing.<br />

• Connect the four color-coded wires to the Sensor Interface plug.<br />

Important: Observe the color coding. If wires are not connected<br />

to the proper terminals, the leak detection system cannot operate<br />

properly.<br />

• Insert the sensing cable (SI) plug into the SI socket (item 20 on<br />

the product illustration on the first page).<br />

Install zener barrier, if applicable.<br />

When sensing cable will be located in Class I, Division 1 locations,<br />

approval agencies require that the sensing cable be protected<br />

with a zener barrier between the sensing cable <strong>and</strong> the<br />

TTDM module. A zener barrier may also be used to provide<br />

lightning protection for the module when the sensing cable may<br />

be exposed to electrical discharges. Contact Raychem to select<br />

the proper zener barrier.<br />

When installing a zener barrier, wire it in accordance with the<br />

instructions provided with the kit.<br />

TTDM<br />

Ordinary Area<br />

Zener<br />

barrier<br />

Leader or jumper cable<br />

RED GRN YEL BLK AGND<br />

33<br />

34<br />

35<br />

36<br />

37<br />

SENSOR CABLE<br />

PL<br />

Class I, Division 1<br />

(Zone 0 or Zone 1 in Europe)<br />

Hazardous <strong>Location</strong><br />

//// / / / / / / / / / / / / / / / / / / / / / / / / / ///////////// / / / / / / / / / / / / / / / ///////////// / / / / / / / / / / / / / / / / //////////// / / / /<br />

Jumper cable<br />

No connection<br />

to terminal 37<br />

Sensing cable<br />

Connecting the Interfaces<br />

If connecting the 4–20 mA port or the RS-232/RS-485 serial<br />

port, refer to the <strong>TraceTek</strong> TTDM Operation <strong>and</strong> Maintenance<br />

Manual for details.<br />

R<br />

Belgium<br />

NV Raychem SA<br />

Diestsesteenweg 692<br />

3010 Kessel-Lo<br />

Tel (32) 16/351-800<br />

Fax (32) 16/351-797<br />

Korea<br />

Raychem Korea Limited<br />

831-45 Yeuksam-Dong<br />

Kangnam-Ku<br />

Seoul 135<br />

Tel (82) 2/557-7752<br />

Fax (82) 2/558-5765<br />

4<br />

Power up the system.<br />

After connections are complete, supply power to the unit. The<br />

unit will go through a series of self-tests, <strong>and</strong> then display the<br />

system status. If the sensing circuit is complete <strong>and</strong> free of leaks<br />

or other problems, the green Monitoring LED only will illuminate,<br />

<strong>and</strong> the LCD display will appear as follows:<br />

System Normal<br />

16:23 02-Jan-96<br />

If this is not the case, you can find additional information in the<br />

TTDM Operation <strong>and</strong> Maintenance Manual supplied with the<br />

module.<br />

Commissioning<br />

Your system should be commissioned by an authorized<br />

<strong>TraceTek</strong> representative. The system map is a crucial part of a<br />

<strong>TraceTek</strong> locating system. The TTDM will give the point along<br />

the sensing cable at which liquid has been detected; the map is<br />

essential to show its physical location.<br />

Important: Store hardware <strong>and</strong> documentation supplied with<br />

the TTDM in a secure place for later use (commissioning,<br />

connecting interfaces, operating).<br />

United Kingdom<br />

Raychem Ltd.<br />

Faraday Road<br />

Dorcan, Wiltshire SN3 5HH<br />

Tel (44) 1793/572-663<br />

Fax (44) 1793/572-629<br />

United States<br />

Raychem Corporation<br />

Commercial & Industrial<br />

Infrastructure Division<br />

300 Constitution Drive<br />

Menlo Park, CA 94025-1164<br />

Tel (800) 545-6258<br />

Fax (800) 611-2323<br />

© 1996 Raychem Corporation Printed in USA H55471 P/N 261985 4/96 <strong>TraceTek</strong> is a trademark of Raychem Corporation.