DD384402<br />
DD384403<br />
Distribution<br />
Catalogue numbers<br />
The bars are secured by insulated supports. Three<br />
fixed supports, attached to the framework, are<br />
mandatory. If necessary, additional free supports may<br />
be used.<br />
The bars rest on a bottom support.<br />
The table opposite indicates:<br />
b the number and size of the bars to be used,<br />
depending on the permissible current level in the<br />
busbars<br />
b the number of supports required in a cubicle,<br />
depending on the rated short-time withstand current<br />
(Icw).<br />
Above 1600 A, the busbars must be doubled and<br />
installed in two busbar sections, side by side. In this<br />
case, they must be interconnected by three<br />
equipotential links.<br />
The bars are secured by three mandatory fixed supports and<br />
two free supports.<br />
Busbars up to 3200 A.<br />
4<br />
NSYBVS500<br />
NSYAS500<br />
04662<br />
DD381505<br />
DD383350<br />
DD383352<br />
Lateral flat busbars<br />
up to 3200 A<br />
Busbars 10 mm thick<br />
Busbar calculation<br />
Permissible current No. of bars/ No. of supports Icw (kA rms/1 s)<br />
for switchboards phase<br />
IP55 25 30 40 50 60 65 75 85<br />
1080 1 bar 50 x 10<br />
1250<br />
1600<br />
1 bar, 60 x 10<br />
1 bar, 80 x 10<br />
5 7<br />
9<br />
1850 2 bars, 50 x 10 3<br />
2000 2 bars, 60 x 10<br />
2500 2 bars, 80 x 10<br />
3200 2 bars, 100 x 10<br />
Note: The permissible current values for the busbars are given for an ambient temperature of<br />
35 °C around the switchboard.<br />
For more information on busbar calculations, see DESW016<br />
Busbar selection<br />
Flat busbars, W 1675 mm<br />
Designation Cat. no.<br />
Copper bar with holes 50 x 10 04525<br />
Copper bar with holes 60 x 10 04526<br />
Copper bar with holes 80 x 10 04528<br />
Busbar supports : directly fixed on frame (300 mm width duct)<br />
Three fixed supports are required to maintain the busbars. If more than 3 supports<br />
are required, use additional free supports.<br />
Designation Cubicle W 300<br />
D 500 D 800 D 800<br />
Distance between busbar<br />
centres<br />
Fixed support for lateral flat<br />
busbars<br />
75 75 115<br />
NSYBVS500 NSYBVS800 NSYBVS800L<br />
Free support (additional) 04662 04662 04678<br />
NSYBVS500. 04662.<br />
Busbar chocks<br />
The bottom support maintains the bars in position. It is not considered a busbar<br />
support.<br />
Designation Cubicle W 300<br />
D 500 D 800<br />
Distance between busbar<br />
centres<br />
Bottom support for lateral flat<br />
busbars<br />
NSYAS500.<br />
DD381650<br />
75 75 115<br />
NSYAS500 NSYAS800 NSYAS800L<br />