Distribution<br />

Catalogue numbers<br />

The bars are secured by insulated supports. Three<br />

fixed supports, attached to the framework, are<br />

mandatory. If necessary, additional free supports may<br />

be used.<br />

The bars rest on a bottom support.<br />

The table opposite indicates:<br />

b the number and size of the bars to be used,<br />

depending on the permissible current level in the<br />

busbars<br />

b the number of supports required in a cubicle,<br />

depending on the rated short-time withstand current<br />

(Icw).<br />

Above 1600 A, the busbars must be doubled and<br />

installed in two busbar sections, side by side. In this<br />

case, they must be interconnected by three<br />

equipotential links.<br />

The bars are secured by three mandatory fixed supports and<br />

two free supports.<br />

Busbars up to 3200 A.<br />

4<br />

NSYBVS500<br />

NSYAS500<br />

04662<br />

DD381505<br />

DD383350<br />

DD383352<br />

Lateral flat busbars<br />

up to 3200 A<br />

Busbars 10 mm thick<br />

Busbar calculation<br />

Permissible current No. of bars/ No. of supports Icw (kA rms/1 s)<br />

for switchboards phase<br />

IP55 25 30 40 50 60 65 75 85<br />

1080 1 bar 50 x 10<br />

1250<br />

1600<br />

1 bar, 60 x 10<br />

1 bar, 80 x 10<br />

5 7<br />

9<br />

1850 2 bars, 50 x 10 3<br />

2000 2 bars, 60 x 10<br />

2500 2 bars, 80 x 10<br />

3200 2 bars, 100 x 10<br />

Note: The permissible current values for the busbars are given for an ambient temperature of<br />

35 °C around the switchboard.<br />

For more information on busbar calculations, see DESW016<br />

Busbar selection<br />

Flat busbars, W 1675 mm<br />

Designation Cat. no.<br />

Copper bar with holes 50 x 10 04525<br />

Copper bar with holes 60 x 10 04526<br />

Copper bar with holes 80 x 10 04528<br />

Busbar supports : directly fixed on frame (300 mm width duct)<br />

Three fixed supports are required to maintain the busbars. If more than 3 supports<br />

are required, use additional free supports.<br />

Designation Cubicle W 300<br />

D 500 D 800 D 800<br />

Distance between busbar<br />

centres<br />

Fixed support for lateral flat<br />

busbars<br />

75 75 115<br />

NSYBVS500 NSYBVS800 NSYBVS800L<br />

Free support (additional) 04662 04662 04678<br />

NSYBVS500. 04662.<br />

Busbar chocks<br />

The bottom support maintains the bars in position. It is not considered a busbar<br />

support.<br />

Designation Cubicle W 300<br />

D 500 D 800<br />

Distance between busbar<br />

centres<br />

Bottom support for lateral flat<br />

busbars<br />

NSYAS500.<br />

DD381650<br />

75 75 115<br />

NSYAS500 NSYAS800 NSYAS800L<br />

version: 1.0 - 06/2010 401F_E22315.indd