DD384405<br />

DD384406<br />

DD383399<br />

Distribution<br />

Catalogue numbers<br />

To satisfy safety clearances, the assembly points on adjacent<br />

bars must be staggered as shown above.<br />

401F_E22315.indd<br />

DD380512<br />

DD383398<br />

Lateral flat busbars<br />

up to 1600 A<br />

Busbars 5 mm thick<br />

Horizontal-busbar connections<br />

Direct connection (115 mm between centres)<br />

The connection between horizontal busbars, 5 mm thick, and lateral flat busbar is<br />

direct, after drilling the bars.<br />

Drilling diagram for horizontal busbars, 5 mm thick.<br />

Direct connection (75 mm between centres)<br />

For busbars with 75 mm between centres, the bars must fully overlap.<br />

Drilling diagram for horizontal busbars, 5 mm thick<br />

Number of assembly screws (04645)<br />

Horizontal bars (mm) Vertical bars (mm)<br />

50 60 80<br />

50 2 2 2<br />

60 - 2 2<br />

80 - - 3<br />

In case of direct connection (75 or 115 mm centre distance) with a horizontal<br />

busbars, bottom support part no. NSYAS500, NSYAS800 or NSYAS800L are not<br />

required.<br />