Prisma Plus PH System - Schneider Electric
Prisma Plus PH System - Schneider Electric
Prisma Plus PH System - Schneider Electric
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
DD384405<br />
DD384406<br />
DD383399<br />
Distribution<br />
Catalogue numbers<br />
To satisfy safety clearances, the assembly points on adjacent<br />
bars must be staggered as shown above.<br />
401F_E22315.indd<br />
DD380512<br />
DD383398<br />
Lateral flat busbars<br />
up to 1600 A<br />
Busbars 5 mm thick<br />
Horizontal-busbar connections<br />
Direct connection (115 mm between centres)<br />
The connection between horizontal busbars, 5 mm thick, and lateral flat busbar is<br />
direct, after drilling the bars.<br />
Drilling diagram for horizontal busbars, 5 mm thick.<br />
Direct connection (75 mm between centres)<br />
For busbars with 75 mm between centres, the bars must fully overlap.<br />
Drilling diagram for horizontal busbars, 5 mm thick<br />
Number of assembly screws (04645)<br />
Horizontal bars (mm) Vertical bars (mm)<br />
50 60 80<br />
50 2 2 2<br />
60 - 2 2<br />
80 - - 3<br />
In case of direct connection (75 or 115 mm centre distance) with a horizontal<br />
busbars, bottom support part no. NSYAS500, NSYAS800 or NSYAS800L are not<br />
required.<br />
version: 1.0 - 06/2010<br />
3