DD384396<br />

Distribution<br />

Catalogue numbers<br />

The bars are secured by insulated supports attached to<br />

the framework.<br />

The tables opposite indicate:<br />

b the number and size of the bars to be used,<br />

depending on the permissible current level in the<br />

busbars<br />

b the number of busbar supports for each type of<br />

framework, depending on:<br />

v the size of the busbars<br />

v the rated short-time withstand current Icw.<br />

For more information on busbar calculations, see<br />

DESW016.<br />

The modularity of the busbar is 3 modules.<br />

2<br />

Horizontal busbars<br />

Up to 3200 A<br />

Flat copper bars 10 mm thick<br />

Busbar calculation<br />

Number and size of copper busbars<br />

Permissible current (A) No. of bars/phase<br />

IP55<br />

1080 1 bar de 50 x 10<br />

1250 1 bar de 60 x 10<br />

1600 1 bar de 80 x 10<br />

1850 2 bars de 50 x 10<br />

2000 2 bars de 60 x 10<br />

2500 2 bars de 80 x 10<br />

2900 2 bars de 100 x 10<br />

Note: the permissible current values for the busbars are given for an ambient temperature of<br />

35 °C around the switchboard.<br />

Number of supports (distance between centres: 75 mm)<br />

Framework width<br />

(mm)<br />

Size of bars<br />

(mm)<br />

No. of supports Icw (kA rms/1 s)<br />

y 25 y 30 y 40 y 50 y 60 y 65 y 75 y 85<br />

W 700 mm 1 bar de 50 x 10<br />

1 bar de 60 x 10<br />

1 bar de 80 x 10<br />

3<br />

4<br />

2 bars de 50 x 10<br />

2 bars de 60 x 10<br />

2 bars de 80 x 10<br />

2 bars de 100 x 10<br />

2<br />

W 300 mm All sizes 1 2<br />

Number of supports (distance between centres: 115 mm)<br />

Framework width<br />

(mm)<br />

Size of bars<br />

(mm)<br />

No. of supports Icw (kA rms/1 s)<br />

y 25 y 30 y 40 y 50 y 60 y 65 y 75 y 85<br />

W 700 mm 1 bar de 50 x 10<br />

1 bar de 60 x 10<br />

1 bar de 80 x 10<br />

2 bars de 50 x 10<br />

2 bars de 60 x 10<br />

2 bars de 80 x 10<br />

2 bars de 100 x 10<br />

2<br />

3 4<br />

W 300 mm All sizes 1 2<br />