01.06.2013 Views

user manual - Lohberger Heiz

user manual - Lohberger Heiz

user manual - Lohberger Heiz

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

7. Requirements for the room where the appliance is situated<br />

Floor - load capacity<br />

B*<br />

page 8<br />

Prior to installing the appliance, make sure that the substructure<br />

of the floor is suitable to bear the weight of the appliance.<br />

Ensure that the stove is positioned horizontally and without<br />

vibration.<br />

8. Air supply connection from outside (accesory)<br />

Accessory:<br />

Air supply connection<br />

pellets module ø 50 mm<br />

A 20<br />

DN 100<br />

30<br />

DN 50<br />

85<br />

15*<br />

•… for an appliance height of 85<br />

cm<br />

fig. 3<br />

Accessory:<br />

Air supply connection stove ø 100<br />

mm (see <strong>user</strong> <strong>manual</strong> stove)<br />

Wall opening to<br />

be provided by<br />

the customer<br />

fig. 4<br />

Gerät<br />

Seitenabstand Bodenabstand<br />

A<br />

B<br />

LCP 70 (F1+B1+P) 21 33<br />

LCP 75 A (F1+B2+P) 21 33<br />

LCP 75 B (F2+B1+P) 23,5 33<br />

LCP 75 B-Z (F2+B1+P+Z) 23,5 19,5<br />

LCP 80 (F2+B2+P) 23,5 33<br />

LCP 80-Z (F2+B2+P+Z) 23,5 19,5<br />

table 2<br />

Room and ambient temperatures /humidity<br />

The appliance is suitable for rooms with normal humidity and<br />

room temperatures ranging from +5 °C to +20 °C. Should room<br />

temperatures fall below 5 °C, it is imperative to add appropriate<br />

antifreeze to the water.<br />

The appliance is not splash proof; therefore it must not be<br />

installed in wet rooms such as bathroom units.<br />

Basically, the appliance is dependent on indoor air, that means the air supply<br />

needed for combustion is extracted from the room where the appliance is<br />

positioned. Subsequently air supply is to be provided from outside by means<br />

of a ventilation opening. To do this, an opening of 10-15 cm in diameter has to<br />

be provided at one exterior wall of the room where the appliance is located.<br />

Outside a stable protective grating is to be fitted. Furthermore, at places where<br />

strong winds are prevalent or places which are exposed to weather, a protection<br />

against wind and rain is required.<br />

If it is not possible to provide an opening to the outside from the room where<br />

the appliance is positioned, it is also possible to create an opening in an adjoining<br />

room. Make sure that the adjoining room has a permanent connection<br />

to the room where the pellet stove is positioned by means of a ventilation<br />

grate.<br />

If there are additional heating units in the same room, the ventilation openings<br />

must provide adequate air supply for combustion to ensure proper operation<br />

of all appliances!<br />

Too low pressures in the room where the appliance is located (e.g. caused by<br />

ventilation systems, extractor hoods etc.) or in the pellets container (e.g. caused<br />

by pneumatic appliances) are likely to impair the functioning of the fire place and<br />

their safety (technique) and are therefore not permitted.<br />

Air supply connection from outside (optional equipment)<br />

To ensure a sufficient supply of combustion air in the case of tightly sealed<br />

windows and low-energy houses equipped with ventilation systems or when<br />

ducted extractor hoods are used, it may be necessary to provide fresh combustion<br />

air from outside.<br />

Even with an outdoor air connection the requirements for an operation that is<br />

independent from the ambient air are not fulfilled!<br />

The dimensions for fitting are shown in „Figure 4“ as well as „Table 2“. Please<br />

note the changes to the dimensions due to the adjustment of the height of the<br />

appliance or of the stove frame.<br />

• It is not allowed to install shut-off devices (flaps, dampers, …) in the air<br />

supply line!<br />

• The air supply line consisting of non-combustible materials must be a maximum<br />

of 4 m in length and must not have too many bends!<br />

• To avoid condensation, the air supply line must be insulated!<br />

• The air flue must be at least 50 or 100 mm, respectively, in diameter. If<br />

rectangular tubes are used, they must maintain the appropriate diameter!<br />

• If the air supply line runs directly to the outside, it has to be protected<br />

against wind!<br />

• The supply of external combustion air from above may only be provided by<br />

means of chimney systems which have been approved by us..<br />

For the technical acceptance of the heating system, the chimney sweep is required<br />

to check the entire installation, in particular for sufficient combustion air supply.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!