Pour out the powder and check to ensure that no granulation or checking has occurred. Change<br />

powder if granulation or caking has occurred. Replace inner shall. Fit cartridge to the cartridge<br />

holder and screw on the cap tightly. Replace safety clip on cap.<br />

Check the trigger nozzle for clogging and clean if necessary. Clean and polish externally.<br />

On completion of the inspection, necessary entries shall be made in the extinguisher register<br />

and the date of last inspection on the extinguisher changed.<br />

ii) As directed by CSVO/SO(FF)/ASO(FF) the extinguishers of this type on charge shall be<br />

tested every year. The test shall be carried out by actually operating the extinguisher and watching for<br />

satisfactory performance specified below :<br />

Capacity of<br />

Extinguisher<br />

Kg.<br />

5<br />

Minimum<br />

duration of<br />

effective<br />

discharge<br />

Seconds<br />

15<br />

Maximum period<br />

for 90%<br />

discharge of the<br />

charge<br />

Seconds<br />

15<br />

Range of throw of<br />

jet<br />

M.<br />

3.5 to 5.5<br />

Advantage shall be taken of this test to give practice in operating them to the staff employed in<br />

the premises where the extinguishers selected for test are located.<br />

The extinguishers shall be polished externally.<br />

On completion of the test, necessary entries shall be made in the Fire Fighting Register and the<br />

date of last inspection on the extinguisher changed.<br />

d) Pressure Test :<br />

As directed by CSVO/SO(FF) this test shall be carried out once in five years in the manner<br />

described earlier except that these extinguishers are to be tested at a pressure of 31.5 kg./cm. 2.<br />

Before recharging, the extinguishers shall be bone dry. After the test the extinguishers shall be<br />

cleaned and polished externally.<br />

On completion of the test, necessary entries ahall be made in the Fire Extinguisher Register<br />

and the date of last pressure test changed.<br />

CIVIL DEFENCE :<br />

Civil Defence is the measure adopted by the Civilian Population in order to minimize the loss of people,<br />

property and industrial production before/during and after the war and also to minimize the effects of enemy action<br />

and to undertake rehabilitation of the victims. This is achieved through boosting of morale of the people.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!