07.05.2013 Views

INSTRUCTIONS MANUAL FOR - Pres-Vac Engineering Aps

INSTRUCTIONS MANUAL FOR - Pres-Vac Engineering Aps

INSTRUCTIONS MANUAL FOR - Pres-Vac Engineering Aps

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

OWNER:<br />

INSTRUCTION <strong>MANUAL</strong> <strong>FOR</strong><br />

TYPE 2389<br />

SYSTEM DESCRIPTION<br />

AND OPERATING/MAINTENANCE<br />

<strong>INSTRUCTIONS</strong> <strong>FOR</strong><br />

HS-ISO-VAC<br />

VACUUM VALVE<br />

REV. 2<br />

CUSTOMER IN<strong>FOR</strong>MATION<br />

HULL NO.:<br />

PRES-VAC REF. NO.:<br />

PRES-VAC ENGINEERING A/S PHONE: +45 4817 4055<br />

SVANEVANG 3-5 TELEFAX: +45 4817 1788<br />

DK-3450 ALLERØD E-mail: presvac@pres-vac.com<br />

DENMARK


INSTRUCTION <strong>MANUAL</strong><br />

CONTENTS<br />

HS-ISO VACUUM VALVE<br />

Page 2 of 21<br />

Rev. 2 April 15, 2003<br />

1. Functional System Description ....................................................................................... 3<br />

1.1. General ................................................................................................................... 3<br />

1.1.1 Ordering Information ................................................................................................ 3<br />

1.2. Design .................................................................................................................... 3<br />

1.2.1 Product Suitability .................................................................................................... 3<br />

1.3. Function .................................................................................................................. 3<br />

1.3.1 Inspection ............................................................................................................... 4<br />

1.4. Capacity .................................................................................................................. 4<br />

2. Operating Instructions ................................................................................................... 4<br />

2.1. Installation .............................................................................................................. 4<br />

2.1.1 Service restrictions ................................................................................................... 4<br />

2.2. Operation ................................................................................................................ 4<br />

2.2.1. Drainage ................................................................................................................. 5<br />

2.2.2. Deposit indicator ..................................................................................................... 5<br />

2.2.3. Damaged Seals ....................................................................................................... 6<br />

2.2.4. Flushing Port ............................................................................................................ 6<br />

2.2.5. Optional Features ..................................................................................................... 7<br />

3. Maintenance Instructions ............................................................................................... 8<br />

3.1. General ................................................................................................................... 8<br />

3.1.1. Inspection ............................................................................................................... 8<br />

3.2. Corrosion Protection.................................................................................................. 8<br />

3.2.1. Coating Repair ......................................................................................................... 8<br />

3.3. Safety Regulations For Maintenance Work ................................................................... 8<br />

3.4. Onboard Verifying Of Set-<strong>Pres</strong>sure .............................................................................. 9<br />

3.5. Directions For Disassembly / Assembly And Cleaning ................................................... 10<br />

4. Spares ........................................................................................................................... 12<br />

DRAWING NO. 2389-1 (Spare Part Ordering List) ................................................................ 13<br />

5. Trouble-Shooting .......................................................................................................... 14<br />

6. Laboratory Report, Summary ........................................................................................ 17<br />

Enclosures:<br />

(1) Flow Charts<br />

(2) Product Review Document<br />

(2) Certificates<br />

(3) Workshop Test Certificate<br />

(4) Maintenance Log Sheet<br />

Page


INSTRUCTION <strong>MANUAL</strong><br />

HS-ISO VACUUM VALVE<br />

1. Functional System Description<br />

1.1. General<br />

Page 3 of 21<br />

Rev. 2 April 15, 2003<br />

The purpose of this vacuum valve is to provide automatic control of pressure conditions during<br />

discharging, voyage, and de-ballasting without any manual operation. Additionally, the vacuum valve<br />

protects the tank against excessive vacuum, when the gas return line is connected to the shore facility<br />

and when loading is carried out with forced suction of vapour to the shore 1) , in accordance with the<br />

VECS-requirements. Furthermore, this vacuum valve provides active protection against fire and<br />

explosions on deck, in terms of preventing a passage of flame into the protected tank.<br />

1.1.1. Ordering Information<br />

Ordering information according to ISO 15364 should be provided by the customer, if not, it is the<br />

customers responsibility that service restrictions, tank pressure limitations, etc. are adhered to.<br />

1.2. Design<br />

The vacuum valve consists of a valve housing with a movable vacuum disc and stem. Correct function of<br />

the valve is tested by check-lifting the movable parts by means of pressing the check-lift handle (or<br />

button on some versions) beneath the vacuum unit from its lower position to its upper position. The<br />

check-lift is designed to be self-closing.<br />

1.4. Capacity<br />

WARNING! The attending crew must be familiar with the normal friction in the system in<br />

This valve is specifically designed with a view to address in-service maintenance, allow inspection of all<br />

vital parts from the outside without use of tools, and allow wear parts to be replaced in-situ. Essential<br />

functions are reflected by indicators, which are clearly visible from the outside at all times. The system<br />

has the simplicity of a weight-loaded design, while adding the in-service advantages of large net<br />

clearances through gas passage-ways to minimize clogging due to fouling from residue/condensate.<br />

1.2.1. Product Suitability<br />

Besides from complying with ISO 15364, a valve design has to be elaborated on in a Product Review<br />

Document, a product drawing and a manual. The ISO standard does not provide any measures against<br />

which a design can be constructed and considered as being “in conformity”. The standard merely<br />

provides general guidelines and, in particular, recommendations for maintenance. It is exclusively the<br />

owner´s/user´s responsibility to ensure that the valve is adequate for the actual installation and the<br />

usage intended. The owner/user shall do this on basis of:<br />

- A product Review Document describing the valve on basis of ISO 15364.<br />

- A product drawing<br />

- IMO MSC/Circ. 677/1009 certification<br />

- Certified service instructions<br />

- This manual<br />

It is the owner´s and or user´s responsibility to review and establish that the selected valve is correctly<br />

sized according to USCG (VECS) rules and IMO MSC/Circ. 731, and made in a design that will match the<br />

available efforts for maintenance. Various types of valves with different maintenance requirements are<br />

available in the PRES-VAC range with escalating prices for less maintenance requiring types.<br />

1.3. Function<br />

order to valuate when cleaning is required. Being able to activate the check-lift<br />

itself by applying great force does not mean that the moveable parts are freely<br />

moving.<br />

<strong>Vac</strong>uum build-up in the cargo tank forces the vacuum disc from its seat (opening pressure). When the<br />

tank vacuum again drops to the valve´s preset level, the disc will re-seat. For details of the performance<br />

characteristics, please refer to the certified flow charts as enclosed.<br />

1) Some applications are subject to requirements stating that the capacity shall also cover the loading rate + vapour growth rate.<br />

Confer with the flow chart as this is not always the case.


INSTRUCTION <strong>MANUAL</strong><br />

1.3.1. Inspection<br />

HS-ISO VACUUM VALVE<br />

Page 4 of 21<br />

Rev. 2 April 15, 2003<br />

Due to the relatively large net clearance through the valve, the inner parts are much less sensitive to<br />

deposits than ordinary designs. If no thick deposits are detected by means of the fouling indicator pins<br />

and by visual inspection after removal of the seat-beds in case of any doubts, the valve is in working<br />

condition and no further precautions are necessary. The allowable thickness of deposits before further<br />

inspection and, as appropriate, cleaning is necessary at a total diameter of the fouling pin of 12 mm. This<br />

measure, however, is only indicative and does not substitute visual inspection after removal of the seat-<br />

bed. See section 2.2.2.<br />

1.4. Capacity<br />

The valve's capacity is rated in standard air. For conversion to maximum loading rates for different<br />

cargoes, please refer to the MASTER'S LOADING CHART as per latest revision of IMO MSC/CIRC. 731.<br />

Other considerations are required for gas collection systems where the vacuum capacity shall equal the<br />

possible suction rate from shore. Please contact <strong>Pres</strong>-<strong>Vac</strong> <strong>Engineering</strong> for further guidance on this<br />

subject.<br />

2. Operating Instructions<br />

CAUTION! Transport, storage and handling of the valve shall take place in upright position.<br />

2.1. Installation<br />

Remove all packing material.<br />

Normally, the vacuum valve and pressure valve are delivered as one unit. For further information, refer<br />

to Instructions Manual for HS-ISO <strong>Pres</strong>sure Valve, section 2.<br />

If this is not the case, installation is accomplished by bolting the valve flange to the tank vent pipe's<br />

mating flange with a suitable gasket between. Check-lift to verify unobstructed movement of disc. Follow<br />

IMO MSC/Circ. 731 pressure drop calculation during system check to verify correct function.<br />

2.1.1 Service Restrictions<br />

See CE certificate for:<br />

1. Minimum MESG of cargo vapour.<br />

2. Minimum vacuum relief setting.<br />

3. Maximum fouling level: See this manual.<br />

4. Maintenance procedures must be observed for proper function of the equipment.<br />

2.2. Operation<br />

Before loading, discharging, and de-ballasting the valve must be check-lifted to ascertain free movability<br />

of the vacuum disc. Correct check-lifting is accomplished by pulling the check-lift handle (or pushing the<br />

button, if no check-lift handle) from its lower position (fig.1) to its upper position (fig. 2) and back again.<br />

The check-lift is self-closing when in proper maintained condition. If not, it should be cleaned and the rest<br />

of the valve inspected/cleaned.<br />

1.4. WARNING! Capacity The attending crew must be familiar with the normal friction in the system in<br />

The valve's capacity order is to rated valuate in standard when air. cleaning For conversion is required. to maximum Being able loading to activate rates for the different check-lift cargoes,<br />

please refer to itself the MASTER'S by applying LOADING great force CHART does as not per mean latest that revision the of moveable IMO MSC/CIRC. parts are 731. freely Other<br />

considerations are required for gas collection systems where the vacuum capacity shall equal the possible<br />

moving.


INSTRUCTION <strong>MANUAL</strong><br />

HS-ISO VACUUM VALVE<br />

Fig. 1. Check-Lift closed Fig. 2. Check-Lift open<br />

Page 5 of 21<br />

Rev. 2 April 15, 2003<br />

During normal voyage, the vacuum valve type ISO operates automatically and equalizes vacuum caused<br />

by thermal variations.<br />

WARNING! As per SOLAS-requirements, check-lifting must be carried out before loading,<br />

2.2.1. Drainage<br />

The valve is self-draining due to large net clearances and no horizontal surfaces on the inside of the<br />

valve.<br />

2.2.2. Deposit Indicator<br />

discharging or ballasting is commenced. If the valve does not move freely,<br />

the cause should be determined and corrected immediately.<br />

To examine for build-up of residue in the valve, unscrew the Plug with deposit indicator (pos. 23 on fig.<br />

16, page 10) and check it for residue thickness. If the residue thickness is over 1 mm. (= pin diameter<br />

over 12mm), cleaning of the interior of the valve is necessary. The cleaning method depends on the<br />

cargo type, but basically paragraph 3.5 should be followed. For certain crystallizing cargoes, heating<br />

arrangement may be necessary according to the chemical code.


INSTRUCTION <strong>MANUAL</strong><br />

2.2.3. Damaged seals.<br />

HS-ISO VACUUM VALVE<br />

Page 6 of 21<br />

Rev. 2 April 15, 2003<br />

It is of outmost importance that the seals are kept in a good condition and are changed before<br />

reassembly, as necessary, to maintain leakage-free operation.<br />

Consequences of damaged or missing seals are as follows:<br />

Type of seal Damaged seal Missing seal<br />

O-rings in flange connections Small leak of cargo or inert gas. Leak of cargo or inert gas.<br />

Small salt water ingress in tank<br />

O-rings in Disc unit Small leak of cargo or inert gas. Leak of cargo or inert gas.<br />

Small salt water ingress in tank<br />

Gasket for Plug w. deposit indicator Leak of cargo or inert gas. Leak of cargo or inert gas.<br />

2.2.4. Flushing Port<br />

Small salt water ingress in tank.<br />

When loading a new cargo, for which cleaning of the HS-ISO <strong>Vac</strong>uum Valve and vent pipe is required,<br />

this procedure is to be followed:<br />

1) Unscrew the flushing plug (pos. 23) on fig. 16 (only when the tank is depressurized).<br />

2) Connect the hose with the cleaning fluid to the flushing port.<br />

3) Start cleaning.<br />

4) Remove the hose and mount the flushing plug.<br />

Fig. 3. Flushing of HS-ISO vacuum Valve<br />

WARNING !<br />

The flushing system may only<br />

be used when it is otherwise<br />

safe to clean the piping.


INSTRUCTION <strong>MANUAL</strong><br />

2.2.5. Optional Features<br />

HS-ISO VACUUM VALVE<br />

Optional accessories for special requirements are available.<br />

Page 7 of 21<br />

Rev. 2 April 15, 2003<br />

Fig. 5: Proximity switch for Fig. 6: Fixture for forced Fig. 7: Zero emission kit<br />

stand-by valves closing for PO service for special cargo<br />

Fig. 8: Heating Arrangement Fig. 9: Side mounted Fig. 10: Dual nozzle for im-<br />

(other versions are Gas Freing Cover proved gas disper-<br />

available depending sion of small volume<br />

on size)<br />

Fig. 11: Self closing valve Fig. 12: Gas freeing Cover Fig. 13: Dessicator to prevent<br />

to prevent cargo damage to hygroscopic<br />

escape from sun- cargo<br />

ken vessel


INSTRUCTION <strong>MANUAL</strong><br />

3. Maintenance Instructions<br />

3.1. General<br />

HS-ISO VACUUM VALVE<br />

Page 8 of 21<br />

Rev. 2 April 15, 2003<br />

As per SOLAS-requirements, the following service intervals shall be followed as a minimum:<br />

A.<br />

After 6 months of operation, the valve shall be inspected for proper function and, if necessary, be<br />

cleaned. However, we recommend that the valve be inspected more often depending on the cargo type.<br />

If the check-lift handle does not operate freely, cleaning is required.<br />

B.<br />

After further 6 months of operation, the valve shall be taken apart and cleaned.<br />

Dismounting the valve house, see fig. 16 on page 10, provides access to do the necessary cleaning, i.e.,<br />

pull of the seat bed and all parts are accessible.<br />

3.1.1 Inspection<br />

Due to the relatively large net clearance through the valve, the inner parts are much less sensitive to<br />

deposits than ordinary designs. If no thick deposits are detected by means of the fouling indicator pins<br />

and by visual inspection after removal of the seat-beds in case of any doubts, the valve is in working<br />

condition and no further precautions are necessary.<br />

3.2. Corrosion Protection<br />

When repairing the coating follow the instructions from the producer of the coating quality referred to in<br />

the vessel´s general manual.<br />

3.2.1. Coating Repair<br />

Due to the large inner clearance the valve will not block because of surface corrosion, and repairing of<br />

the coating is therefore not necessary from a valve functional aspect, only if the cargo vapor is damaging<br />

to the main body parts.<br />

3.3. Safety Regulations For Maintenance Work<br />

Spark free tools should be used if maintenance work is carried out while the valve is mounted on the<br />

cargo tank.<br />

WARNING! All maintenance work must be carried out with necessary precautions in<br />

regard to the cargo’s flammability and toxicity.<br />

NOTE! Before dismounting the seat bed and replacing with a new one – the tank pressure<br />

should be lowered to the same level as when performing ullage measurement<br />

through an open deck valve.


INSTRUCTION <strong>MANUAL</strong><br />

HS-ISO VACUUM VALVE<br />

3.4. Onboard Verifying Of the Set-<strong>Pres</strong>sure<br />

Page 9 of 21<br />

Rev. 2 April 15, 2003<br />

After overhaul, verifying of the set-pressure is recommended. This can be accomplished by either<br />

removing the top cover and controlling the pull-weight of the vacuum disc with a PRES-VAC<br />

Dynamometer and confer with PRES-VAC or use the PRES-VAC Test Rig, type TR or TRM, see fig. 14 and<br />

15 below.<br />

The actual valve set-pressure is stamped on the valve body.<br />

The Test Rig, type TR or TRM, is used for onboard verifying of the set-pressure as well as measurement<br />

of the leakage rate to ensure compliance with environmental regulations.<br />

For further details on type TR or TRM and Dynamometer, please refer to a separate manual. This<br />

equipment can be purchased from PRES-VAC.<br />

Fig. 14: Test Rig Fig.15: Dynamometer<br />

(Mechanical and Ex versions are also available)


INSTRUCTION <strong>MANUAL</strong><br />

HS-ISO VACUUM VALVE<br />

Page 10 of 21<br />

Rev. 2 April 15, 2003<br />

3.5. Directions For Disassembly / Assembly And Cleaning<br />

Normal cleaning and inspection, see fig. 16:<br />

1. Remove the Interior of the <strong>Vac</strong> unit by unscrewing the bolts (pos. 32) and washers (pos. 33).<br />

Disassembly of the filter unit:<br />

2. Remove the Screws (pos. 34) and Washers (pos. 35).<br />

3. Tilt the filter element assembly slightly and pull it from the Flange (pos. 2).<br />

4 Remove the check-lift assembly by unscrewing the Nuts (pos. 13).<br />

5. Push carefully the filter element out (pos. 7).<br />

6. Inspect and clean all parts. Repair or replace damaged parts as appropriate.<br />

CAUTION! Apply an even pressure on the whole surface of the filter element to avoid<br />

damage.<br />

Fig. 16: Assembly Drawing for Inspection and Cleaning of HS-ISO <strong>Vac</strong>uum Valve.


INSTRUCTION <strong>MANUAL</strong><br />

HS-ISO VACUUM VALVE<br />

Assembly after normal cleaning and inspection<br />

1. Assembly is done in the opposite sequence.<br />

Replacement of vacuum seat (pos. 5 on fig. 16)<br />

Page 11 of 21<br />

Rev. 2 April 15, 2003<br />

NOTE! For cleaning we recommend a thin lubrication oil and a brush. If damage on any<br />

1. Unscrew bolts (pos. 32) and remove washers (pos. 33)<br />

2. Pull out the filter unit including the O-ring (pos. 27)<br />

3. Remove the vacuum disc (pos. 4) together with stem (pos. 9), washer (pos. 26) , lock washers<br />

(pos. 11) and nut (pos. 10).<br />

4. Unscrew the seat by means of a key between the ribs.<br />

5. Clean thread and insert new seat after surface lapping.<br />

Assembly<br />

1. Assembly is done in the opposite sequence.<br />

NOTE: Seat-beds can be re-used from PRES-VAC at cost of lapping and re-coating, as necessary.<br />

General<br />

parts is observed, repair or replacement must take place.<br />

CAUTION! Pay attention to filter element during paint work on deck.<br />

Screws and bolts not protected from loosening, should be secured by a suitable adhesive, such as PRES-<br />

VAC part no.: 1323-8.<br />

RECOMMENDATION<br />

Fill in the maintenance log sheet in connection with inspection and service.


INSTRUCTION <strong>MANUAL</strong><br />

4. Spares<br />

HS-ISO VACUUM VALVE<br />

Page 12 of 21<br />

Rev. 2 April 15, 2003<br />

There are no class requirements for carrying spares on board. If spares are required, please use the<br />

following procedure:<br />

1. Take a copy of the inserted drawing no. 2389-1.<br />

2. Identify the components and write the required quantities on the part list.<br />

3. Advise builder of ship and new building number.<br />

4. Advise Vessel name.<br />

5. Advise serial number punched into the flange of the valve.<br />

Fax the drawing to our office in DENMARK.<br />

When we have the above information, our files contain all further details.<br />

When ordering spare parts, please call our office in DENMARK.<br />

Our telefax and E-mail are open 24 hours a day<br />

Telefax No. ....... +45 48 17 17 88<br />

E-mail .............. presvac@pres-vac.com<br />

Our telephone is open during normal office hours<br />

Telephone No.: . +45 48 17 40 55<br />

Our postal address:<br />

PRES-VAC ENGINEERING A/S<br />

Svanevang 3-5<br />

DK-3450 Allerød<br />

Denmark


INSTRUCTION <strong>MANUAL</strong><br />

SPARE PART ORDERING LIST<br />

HS-ISO VACUUM VALVE<br />

Page 13 of 21<br />

Rev. 2 April 15, 2003


INSTRUCTION <strong>MANUAL</strong><br />

5. Trouble-shooting<br />

HS-ISO VACUUM VALVE<br />

Problem Remedy<br />

Tank pressure is too high A.<br />

Tank vacuum is too high<br />

Page 14 of 21<br />

Rev. 2 April 15, 2003<br />

Check in vessel’s Master Loading Chart according to<br />

IMO MSC/Circ. 731 what the maximum permissible<br />

loading rate is and the corresponding loading rate<br />

with corrections for vapor density and vapor growth<br />

rate. Lower loading rate if necessary.<br />

B.<br />

Check that the valve is clean inside and take care of<br />

maintenance as per Section 3 if necessary.<br />

B.1.<br />

Check that the valve disc is able to travel full stroke<br />

by hand-lifting.<br />

B.2.<br />

Check that pressure seat/disc contact area (width)<br />

is not exceeding manufacturer’s recommendations<br />

to avoid a “aero-dynamic” lock (like blowing<br />

between two sheets of paper) as a consequence of<br />

“home-made” repairs.<br />

C.<br />

Check that the piping is unobstructed by cargo<br />

residue etc.<br />

D.<br />

Check that the pressure-tuning knob has not been<br />

tampered with by use of a calibrated test<br />

instrument.<br />

E.<br />

Contact PRES-VAC to check if the configuration of<br />

magnet-power and booster disc arrangement can<br />

be changed for a more suitable performance for the<br />

actual conditions of installation.<br />

A.<br />

Check in vessel’s Master Loading Chart according to<br />

IMO MSC/Circ. 731 what the maximum permissible<br />

discharge rate is. Check that pump is running with<br />

the intended delivery head to avoid unintended high<br />

rates. Lower pump rate if necessary.<br />

B.<br />

Check that the valve is clean inside and take care of<br />

maintenance as per Section 3 if necessary.<br />

B.1.<br />

Check that the valve disc is able to travel full stroke<br />

by hand-lifting.<br />

B.2.<br />

Check that vacuum seat/disc contact area (width) is<br />

not exceeding manufacturer’s recommendations to<br />

avoid a “aero-dynamic” lock (like blowing between<br />

two sheets of paper) as a consequence of “homemade”<br />

repairs.


INSTRUCTION <strong>MANUAL</strong><br />

HS-ISO VACUUM VALVE<br />

Tank vacuum is too high (continued) B.3.<br />

Not fully lifting pressure disc:<br />

The valve is leaking A.<br />

The valve is hammering A.<br />

Page 15 of 21<br />

Rev. 2 April 15, 2003<br />

Check that the vacuum disc’s contact area is dry to<br />

avoid a hydraulic lock.<br />

C.<br />

Check that the piping is unobstructed by cargo<br />

residue etc.<br />

D.<br />

Contact PRES-VAC.<br />

Due to the relative large venting capacity required<br />

according to USCG regulations on Vapor Emission<br />

Control Systems, which for some cargoes are nearly<br />

doubling the actual loading rate, valves may in fact<br />

be handling far less than designed for. Especially<br />

when the sizing procedure did not allow the VECS<br />

capacity to be present at an elevated tank pressure<br />

just below the maximum working pressure. In other<br />

words; a generous provision for venting capacity is<br />

a problem and the valve performance might appear<br />

as chattering or fluttering and can severely reduce<br />

the lifetime of seats and discs.<br />

The remedy available is to consult PRES-VAC for<br />

guidance on adjusting the opening setting and/or<br />

the configuration of the booster plate arrangement.<br />

In extreme cases, for instance for slop tanks<br />

equipped similar to the main cargo tanks, it may be<br />

necessary to install a dual, small capacity unit with<br />

a differing setting making the too large original<br />

valve a stand-by safety unit for the rare maloperating<br />

event.<br />

Clean valve discs and seats.<br />

B.<br />

Check pressure check-lift seal.<br />

C.<br />

Overhaul or replace seats and discs as appropriate.<br />

D.<br />

Contact PRES-VAC.<br />

Check that installation is within the service<br />

restrictions shown in the certification issued by the<br />

CE Notified Body ( <strong>FOR</strong>CE TECHNOLOGY). If not,<br />

contact PRES-VAC.<br />

B.<br />

If the valve is grossly over-sized for the actual<br />

capacity vented, the opening and closing cycle may<br />

reduce the expected lifetime of the sealing parts. If<br />

the differential between the capacity of the valve<br />

based on USCG VCS requirements is too far from<br />

the actual volume vented, the lifetime of the<br />

sealing parts is reduced.


INSTRUCTION <strong>MANUAL</strong><br />

The valve is hammering (continued)<br />

HS-ISO VACUUM VALVE<br />

C.<br />

Page 16 of 21<br />

Rev. 2 April 15, 2003<br />

Check Section 2.2.5 on “Valve Misbehaviour.”<br />

Hammering is by definition non-intended full stroke<br />

movement of the pressure disc and should not be<br />

misunderstood for non-fluttering.<br />

C.1.<br />

Hammering is not an issue with vacuum valves as<br />

these are modulating and therefore unstable in the<br />

opening phase. Since flash-back protection is not<br />

connected with a high velocity nozzle, disc<br />

movement is no concern, save from a lifetime<br />

aspect.<br />

D.<br />

Contact PRES-VAC to check if the configuration of<br />

magnet-power and booster disc arrangement can<br />

be changed for a more suitable performance for the<br />

actual conditions of installation.


LABORATORY REPORT - SUMMARY TESTED IN ACCORDANCE WITH MSC/Circ. 677/1009<br />

6. Laboratory Report, Summary<br />

SUBJECT: HS-ISO VACUUM VALVE<br />

The following report is part of the Instructions Manual as required by MSC/Circ. 677, paragraph 4.3 and<br />

should be kept on board the tanker.<br />

The report contains in a condensed form all conducted tests and results obtained, as well as all further<br />

information required, according to the IMO-rules, MSC/Circ. 677 as amended by Circ. 1009 and ISO<br />

15364.<br />

The complete Laboratory Report and test data including video documentation is on file with Force<br />

Technology, the CE Notified Body. The following tests were completed successfully as indicated on the<br />

attached certificates of Type Approval from Force Technology.<br />

Test<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Description<br />

Corrosion test<br />

Hydraulic pressure<br />

test<br />

Flow test<br />

Flash-back test<br />

Ice test<br />

MSC/Circ.<br />

677/1009<br />

3.5.1<br />

3.5.2<br />

3.3.2<br />

3.2.2<br />

2.3.4<br />

Remarks:<br />

The corrosion tests were carried out on a test rig as<br />

shown on drawing no. 1194-26. The test results were<br />

to the satisfaction of the Notified body.<br />

The hydraulic tests were carried out on a test rig as<br />

shown on drawing no. 1194-317. The test results<br />

were to the satisfaction of the Notified body.<br />

The flow tests were carried out on a test rig as shown<br />

on drawing nos. 1194-148 and 1194-149. The results<br />

obtained appear from the inserted flow curves as<br />

enclosed.<br />

The flash-back tests were carried out on a test rig as<br />

shown on drawing no. 1194-160. In no case did<br />

flash-back occur.<br />

The ice test was carried out on a test rig as shown on<br />

drawing no. 1194-318. The test valve was cooled to<br />

–20 to –30 degrees Celsius. Hereafter the valve was<br />

check-lifted, and it was seen that the valve was fully<br />

operative.<br />

Additionally, separate flow testing has been performed in accordance with API 2000 Standard because<br />

flow testing as per MSC/Circ. 677/Circ. 1009 and ISO15364 does not automatically qualify for API 2000<br />

requirements since higher pressure and vacuum conditions are necessary for some valve configurations.<br />

Please refer to the attached Certificates of Type Approval from Force Technology.


LABORATORY REPORT - SUMMARY TESTED IN ACCORDANCE WITH MSC/Circ. 677/1009<br />

Drawing no.: 1194-26, Corrosion Test<br />

Drawing no.: 1194-317, Hydraulic <strong>Pres</strong>sure Test<br />

SUBJECT: HS-ISO VACUUM VALVE


LABORATORY REPORT - SUMMARY TESTED IN ACCORDANCE WITH MSC/Circ. 677/1009<br />

Drawing no.: 1194-149, Flow test<br />

Drawing no.: 1194-148, Flow Test<br />

SUBJECT: HS-ISO VACUUM VALVE


LABORATORY REPORT - SUMMARY TESTED IN ACCORDANCE WITH MSC/Circ. 677/1009<br />

Drawing no.: 1194-160, Flash-back Test<br />

Drawing no.: 1194-318, Ice Test<br />

SUBJECT: HS-ISO VACUUM VALVE

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!