<strong>Federal</strong> <strong>Commander</strong> <strong>Digital</strong> <strong>System</strong><br />

Use the Select Zone spin control to select the desired zone. A maximum of 99 zones may be<br />

configured in dynamic mode or 16 in conventional mode.<br />

Adding and removing sites<br />

To add sites to the selected zone, highlight the desired sites in the site selection list box on the<br />

left and click Add. To remove a selected site, highlight and click Remove. Click Remove<br />

All to remove all sites from the selected zone.<br />

The currently selected zone configuration is automatically saved when scrolling to another zone<br />

or closing the zone setup window.<br />

Voice Setup (Call-in and Call-out)<br />

Call-in and Call-out are both functions that alert key support personnel to the current status of<br />

The <strong>Commander</strong> <strong>SFCD</strong>WARE <strong>System</strong>. Both functions require the use of a touchtone telephone<br />

line. Pushing the appropriate buttons on the touchtone keypad enters actions and responses to<br />

the messages announced through the voice modem. Call-in and Call-out works similar to a voice<br />

mail system. Simply listen to the voice menus and respond with touchtone digits as desired.<br />

Call-in<br />

Call-in is initiated by dialing the phone number of the line connected to the CCU. The CCU is<br />

programmed to answer the call following a programmable number of rings. The user will be<br />

prompted to enter a password before accessing the system. Any password that is currently in the<br />

call list for any username will be accepted for the Call-in function. Note: Wait for the voice prompt<br />

to end before entering password.<br />

After a valid password is entered, the user may listen to all current alarms in the system. The user<br />

may also Acknowledge Alarms in the system.<br />

Call-out<br />

Call-out is initiated by the <strong>SFCD</strong>WARE <strong>System</strong> software when an alarm condition occurs that has<br />

been selected to call out (e.g. Intrusion) and is not Acknowledged or Reset before the Call-out<br />

Time Delay expires. The Call-out sequence is based on a user priority level from 0-9 with 0 being<br />

the highest priority. There must always be at least one 0 level priority user to enable the Call-out<br />

feature to operate. For the Call-out function, only the password associated with the phone<br />

number called will be considered valid. If the key support person who answers the call<br />

acknowledges even one alarm, the calling sequence is terminated and no other users will be<br />

called until the next Alarm event occurs. If no alarms are Acknowledged, the <strong>SFCD</strong>WARE<br />

<strong>System</strong> will initiate another Call-out in five minutes to the phone number associated with the next<br />

higher priority number, providing the Alarm that triggered the Call-out has not cleared in the<br />

meantime.<br />

114<br />